    Single Phase 208??
    Greetings,
    I'm about to purchase a Suspended unit heater for a carpentry shop. I'd like to use a service I previously used for a table saw, being 208v 30A, (2 hots at 120(120degs opposed) and a ground). The fixtures I'm looking at, in the catalog, state that they are Single/3 phase 208 or Single phase 208. My real confusion here is that I have no idea what single phase 208 is since 208 is derived from 2 legs of a true 3 phase system. Any ideas?

    Thanks
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Dec 12, 2006, 11:31 AM
    So I am assuming that you currently have a 3 phase 4 wire 120/208 volt system?

    For 208 volt single phase, use a two pole breaker, which can connect to any two of the three legs in a phase panel, to get 208 volt 1 phase.

    If you truly have three phase 208 volt, then I would suggest you get a 3 phase heater. But if your circuit you want to use is only as you say two hots and the ground, then you need a single phase 208 volt heater.

    Did this answer your question?
    jwdodson's Avatar
    jwdodson Posts: 5, Reputation: 1
    New Member
     
    #3

    Dec 12, 2006, 11:38 AM
    I see, so something listed as "single phase 208v" is still actually from 2 legs of a 3phase 120v system.
    What is the difference from a single phase 208v and a 3phase 208v if both would ultimately only be using 2 of the hot legs?

    And yes, I do have true 3phase in the building, it's just that when we install the table saw, years ago we ran 10/3 to the branch panel and used a 30A double pole, so on the level where the Heater is going is only 2 hots/ground of a 3phase system.

    It seems like I just got hung up on a nomenclature thing.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #4

    Dec 12, 2006, 11:44 AM
    Single phase 208 circuit will use two hot legs, and a three phase circuit needs all three hot legs.

    All circuits will need the ground.

    If any circuits need 120/208, either 1 phase or 3 phase, then the neutral is needed.
    jwdodson's Avatar
    jwdodson Posts: 5, Reputation: 1
    New Member
     
    #5

    Dec 12, 2006, 11:53 AM
    Okay, that's what I figured (as far as what was meant by 3phase 208v). I was just unsure of what was meant by the single phase 208v. Now I know, thank you much.
    gup93488's Avatar
    gup93488 Posts: 1, Reputation: 1
    New Member
     
    #6

    Aug 28, 2012, 09:04 AM
    I need a little clarifictaion on this subject.

    If single phase voltage is 120. What is the two phase voltage? Is it 208 V or 240V.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #7

    Aug 28, 2012, 09:34 AM
    Two hot legs of a three phase system is still single phase, and would be 208 volts.
    Stuartg46's Avatar
    Stuartg46 Posts: 2, Reputation: 1
    New Member
     
    #8

    Nov 2, 2012, 04:58 PM
    2 phase or polyphase is rarely used, don't even concern yourself with this.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

2-phase vs 3-phase degrees of separation [ 5 Answers ]

At work we have 3-phase power. I understand the oscillations are 120 degrees apart. At home I have 2-phase power. Are the oscillations 180 degrees apart? I understand the neutral on a 240v circuit should carry 0 as the phases cancel each other out. My real question is that if we have a...

Three phase vs. Single phase [ 3 Answers ]

What benefits would you have running a three phase service as opposed to running single phase.

208v single phase wiring [ 1 Answers ]

How do I connect a 208v single phase appliance to my home circuit panel? I installed a 30amp breaker which has 2 connections, red and black (hot), then I have white (neutral), and green for ground. The device only as 2 connectors not 3, plus ground? Thanks

How to view single record of ALL people at single address? [ 5 Answers ]

I have a table with addresses and names. I can easily sort it by address to see all the people living at the same address grouped together. However, this is problematic with mail-merges, since I wind up generating a new letter for each person, sending multiple mailings to the same residence. ...

120v/208v single phase appliance wiring [ 2 Answers ]

Recently purchased a coffee machine that has the above reqts. I understand that it has 220 and 110v circuits that need power. I also purchased a generator to power this brewer outside. If I use a NEMA L14-30P plug, to connect into the generator, What is the sequence of wiring for the plug three...


View more questions Search