    Romex 12-2 temp rating?
    Hello. My first visit to this very informative site. I have a question about wiring in a pole building. I'm using 12-2 Romex simpull on a 20 amp outlet circuit along the walls. My question is, will heat in the summer months on the metal siding be hot enough to damage the wire if it is stapled on the top edge of 2x4 purlins inside the finished wall space? It won't touch the metal siding but will be within a half inch or so from it. I don't want to drill holes through the poles and this looks like a good place to run wiring. If this is OK to do for an ag building, can I run several wires in this space to various circuits? This part of the building will be partitioned off for a machine shop. Hope this makes sense. Thanks.
    robkelly2242's Avatar
    robkelly2242 Posts: 57, Reputation: 0
    Junior Member
     
    #2

    Mar 10, 2008, 11:26 PM
    Probably won't be a problem with the romex degrading from temperature, but the higher temp will heat the wire and drop the current carrying capacity by raising the resistance. Make sure it's fused at no more than 20 amps; if you operate a 2 KVA or higher device for extended periods in the summer, expect the breaker to trip now and then.
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #3

    Mar 11, 2008, 04:32 AM
    At temps up to 140 deg F there is no need to derate the cable.
    As Rob says, keep to the standard 20A breaker and you'll be fine.

    I've shot the hood of my truck and a new blacktop driveway with a digital thermometer in the middle of a 90+ deg day in summer and it was under 140 deg.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Heat not kicking on until the temp dips below 64 degrees, target temp set to 72 [ 2 Answers ]

Hello, This is my first time posting here, but I figured it was a good place to start for some advice. I just bought a new townhouse a few weeks ago and have been having some heating issues since moving in. The actual furnace (Goodman GMS 8045) was installed in June of '06 while the unit was...

Furnace not kicking on when temp drops below thermostat set temp [ 1 Answers ]

I've got a Beckett oil heat water on demand furnace that heats through baseboards. Since this past weekend the furnace hasn't been kicking on when the temperature drops below my set temp of 68 degrees. I have to go down to the furnace and simply touch the top of the reset box for it to kick on. ...

Differential of return temp and cooled exit air temp [ 1 Answers ]

Here is the problem I am having, I had a new unit installed last year on my new house. I noticed that the compressor runs for a long time and shut off for a short period. This got my attention and wondered if the unit is running efficiently. I had my doubts from the start since the A coil looked...

Electrical outlet rating vs. Circuit breaker amperage rating [ 5 Answers ]

Hello to all, I am new to this forum, please excuse me if this question has been answered. I just bought a Thermal Dynamics Plasma cutter. It has a Nema 50-P plug end on it, which I assume is to be plugged into a Nema 50-R outlet. In looking in my reference book, this is a 3 wire...

Temp gauge showing temp, 2001 Chev Malibu [ 13 Answers ]

I have a 2001 Chev Malibu LS, V6, temp gauge is not showing any heat at all, not registering when I know the coolant is hot ? Veh has about 126000 mi on it, never been flushed out, thought I would attempt to flush myself but don't you think the problem might be a bad thermostat ? If so, where and...


View more questions Search