    Outlet grounding
    What problem would happen if the ground wire on an outlet was hooked to the netural white wire?
    Cobraguy's Avatar
    Cobraguy Posts: 140, Reputation: 11
    Junior Member
     
    #2

    Dec 14, 2007, 07:18 AM
    I believe it could put power on the ground circuit. Not good.

    Even though they are joined at the main breaker, you don't get power on the ground circuit. Something about the path of least resistance as I understand it. I'm sure someone with a better electrical engineering back ground can explain it much better than I.
    ballengerb1's Avatar
    ballengerb1 Posts: 27,378, Reputation: 2280
    Home Repair & Remodeling Expert
     
    #3

    Dec 14, 2007, 08:39 AM
    If you ground your neutral you will have likely added all of your plumbing and electric conduit to your electrical circuit. Do not do this. What issue were you trying to fix, maybe we can help solve your problem without creating a new dangerous problem.
    labman's Avatar
    labman Posts: 10,580, Reputation: 551
    Uber Member
     
    #4

    Dec 14, 2007, 11:45 AM
    As bad as that is, only recently have they quit hooking up dryers and ranges that way. On 120 volt circuits, code has long forbid it with good cause. Ground and neutral have different jobs. There is enough safety built into most stuff that it usually takes a couple of things to go wrong before anybody gets hurt or the house burns down. Connecting the ground and neutral is a very effective first step.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #5

    Dec 15, 2007, 08:32 AM
    Using an equipment ground as a return path instead of the neutral will allow current to be sent back on the equipment ground system continuously. This potentially can cause a shock hazard for anyone coming in contact with a grounded surface with a lower impedance that of the energized frame of an appliance.

    Any loose connection in conduit or cable sheathing will create a high resistance connection that will spark and can develop into a fire.

    If you are considering doing this as a solution to a broken neutral, or any other reason,do this at your own risk, and be prepared to be responsible for the damaging effects.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Grounding outlet [ 6 Answers ]

Hey anyone How do I ground a 3 prong outlet and there are only 2 wires one black and one white. No green

Grounding an Outlet [ 22 Answers ]

I am moving into an older house that has only 2-prong outlets. Some are 3-prong, but they are not grounded (I have a power strip that tells you if it is gounded or not). I found this at Ace Hardware....

Grounding an outlet screwed into a light scocket [ 3 Answers ]

Is an outlet screwed into a grounded light socket grounded? I want to screw an outlet into an exterior light socket, then plug the Christmas lights into this outlet but I want the Christmas lights to be grounded. Is there a way to get around taking off the light fixture and installing a box with...


View more questions Search