| "Continous permissable current" is not an issue with a feeder. Here is the text from 215.2(A)(1): "The minimum feeder-circuit conductor size, before the application of any adjustment or correction factors, shall have an allowable ampacity not less than the noncontinuous load plus 125 percent of the continuous load."
Almost nothing in a residence is considered a continuous load, so the 125% does not even really apply.
Do you also agree that the poster needs to use 4/0 conductors???? Come on. Be real.
Besides, voltage drop is NOT the issue here, it is NM-B (romex) in an underground outside conduit.
Do you at least agree that that is highly illegal and not safe (long term)???
And also that the installed used plumbing pipe for the feeder? How about that?
"He doesn't even respect tkrussell's response either."
So by not agreeing with something that is equated to disrespect??? What kind of logic is that.
What is with this place??? If you disagree with the king pins you get ostracized? That's fine, I like playing that game.
I never was much for popularity contests, and I DO NOT mind being the unpopular one, as long as my advice is sound.
TK is not god either. I have seen some pretty ambiguous informations given my him. NO ONE is infallible. I make mistakes too.
If I see misinformation on an electrical DIY message board you can bet I will try and correct that information the best I can, and not just with opinion.
There is too much at stake not to! |