Ask Experts Questions for FREE Help !
Ask
    cmhomeinspect's Avatar
    cmhomeinspect Posts: 5, Reputation: 1
    New Member
     
    #1

    Dec 15, 2007, 08:23 PM
    Neutral wires in an electric panel
    Why is it considered unsafe to double post neutral wires (two neutral wires to one lug on the neutral bar) in an electric panel?
    biggsie's Avatar
    biggsie Posts: 1,267, Reputation: 125
    Ultra Member
     
    #2

    Dec 15, 2007, 09:00 PM
    This is unsafe due to the need to turn off multiple circuit

    Breakers to work on any of the circuits using these wires.

    If a person is working on one circuit and turns off a breaker

    It is possible that the second neutral is carrying current and

    Is a shock hazzard when removed from neutral buss
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #3

    Dec 15, 2007, 09:32 PM
    Simply because the lug is only rated to handle one wire safely. Any more than rated will result in loose connections.
    Stratmando's Avatar
    Stratmando Posts: 11,188, Reputation: 508
    Uber Member
     
    #4

    Dec 16, 2007, 06:40 AM
    It's a code violation also, The code is based on safety, Not necessarily efficiency.
    I forget the exact wording in a paragraph at the start of the Electrical Code, that states just that.
    Cobraguy's Avatar
    Cobraguy Posts: 140, Reputation: 11
    Junior Member
     
    #5

    Dec 16, 2007, 07:47 AM
    Quote Originally Posted by biggsie
    This is unsafe due to the need to turn off multiple circuit

    breakers to work on any of the circuits using these wires.

    If a person is working on one circuit and turns off a breaker

    it is possible that the second neutral is carrying current and

    is a shock hazzard when removed from neutral buss

    Biggsie... I don't believe this has anything to do with that scenario does it? Since the neutrals are all on the same buss anyway, that problem is always present. The only way to ensure your problem doesn't occur is to have the MWC on tied breakers. Or am I misunderstanding what you're saying?
    Stratmando's Avatar
    Stratmando Posts: 11,188, Reputation: 508
    Uber Member
     
    #6

    Dec 16, 2007, 07:58 AM
    Hey Cobra, I'm thinking he meant 4 breakers would need to be turned off to safely work on a neutral problem, if 2 neutrals under one screw. Provided they were all multi circuit.
    Take Care.
    RustyFairmount's Avatar
    RustyFairmount Posts: 165, Reputation: 40
    Junior Member
     
    #7

    Dec 16, 2007, 06:56 PM
    What biggsie said makes sense to me. Here's the scenario:

    Assume every breaker in your panel is on, and all circuits are under load. You turn off one breaker and attempt to remove it's corresponding white from the neutral buss. In the process, the second white pops out and makes contact with you. ZAP!

    This is an excellent question. I don't believe in following code just because it says so. It's always wise to question code so that you can learn the reason why it is that way, and then follow it! Understanding why code exists is always a good thing.
    Stratmando's Avatar
    Stratmando Posts: 11,188, Reputation: 508
    Uber Member
     
    #8

    Dec 17, 2007, 06:44 AM
    Another reason is if neutral is removed on a multi circuit while energized, the 120 Volt circuits using that neutral may go to 240 volts if load or breaker(s) are not turned off.
    labman's Avatar
    labman Posts: 10,580, Reputation: 551
    Uber Member
     
    #9

    Dec 17, 2007, 09:01 AM
    It may be a bad practice, but come on, who is going to shut off one circuit and loosen 2 wires?
    Stratmando's Avatar
    Stratmando Posts: 11,188, Reputation: 508
    Uber Member
     
    #10

    Dec 18, 2007, 05:58 AM
    If I was redoing a neutral connection that was overheated due to loose connection, I would turn off 2 circuits to repair. If 2 neutrals under same screw. 4 circuits need to be turned off.
    Cobraguy's Avatar
    Cobraguy Posts: 140, Reputation: 11
    Junior Member
     
    #11

    Dec 18, 2007, 07:33 AM
    Strat... I may be totally confused here... which isn't that unusual! LOL You are assuming then that both neutrals under the same screw are on MWC's? I totally agree with 4 breakers needing to be switched off if so. If they aren't MWC's, only two would need to be switched off, right?

    I think my original question to Biggsie was worded poorly... and I did misunderstand a bit what he was saying.

    EDIT: I did read this again and saw where you were assuming the circuits were MWC's. So I do agree with you guys that 4 breakers would need to be off. (or better yet, the MWC's would be on tied breakers and you would need to just flip the two sets of breakers)
    Stratmando's Avatar
    Stratmando Posts: 11,188, Reputation: 508
    Uber Member
     
    #12

    Dec 18, 2007, 07:45 AM
    I think we are in agreement. If neutral was only for one circuit, then the 240 volt danger would be eliminated. I was just mentioning a potential danger that may be overlooked(multi circuit needs 2 breakers off to safely disconnect neutral for repair. Take Care
    labman's Avatar
    labman Posts: 10,580, Reputation: 551
    Uber Member
     
    #13

    Dec 18, 2007, 08:44 AM
    Why isn't it required to mark those infernal things? Say you want to work on circuit #24. If it is shared with #22 or #26, you want it off too. So what do you do, throw all 3 and hope it isn't sharing a neutral with #18?

    What about say a red felt tip bracket {= ?
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #14

    Dec 18, 2007, 10:23 AM
    Basically, only qualified and trained personnel belong in a panelboard, and if any work needs to be done, such as disconnecting wires, that person will know what to lookout for before just haphazardly disconnects any wiring.
    Cobraguy's Avatar
    Cobraguy Posts: 140, Reputation: 11
    Junior Member
     
    #15

    Dec 19, 2007, 07:09 AM
    And I believe NEC 2008 does require MWC's to be tied in some way Labman.
    labman's Avatar
    labman Posts: 10,580, Reputation: 551
    Uber Member
     
    #16

    Dec 19, 2007, 10:59 AM
    Ah, progress. I am surprised how long it took to do something about the 3 wire dryers and ranges.

    For a real horror story, see https://www.askmehelpdesk.com/plumbi...ed-161901.html

    In defense of the plumber. He made it work, told the owner it wasn't right, and left the cover on the panel.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Service Panel, Neutral and Ground bars tied? [ 2 Answers ]

In the service panel, both the Neutral bar and Ground bar tied together. Neutral wires tied to the Neutral bar, Ground wires tied to the ground bar in the service panel. Isn't the ground wire than becomes the same as the Neutral wire, or maybe taking part of the current load off from the Neutral...

Grounding/neutral meter box and panel [ 1 Answers ]

I'm istalling a 100 amp service in the yard w/meter for the lake equip. The pole will have 3 conductors from the power transformer to the meter box (neutral an two hots). The ground wire from the ground rod connects at the meter box at the same lugs as the neutral? Yes? Or to the meter box...

Why is the grounding and neutral bus bar connected in the sub panel? [ 1 Answers ]

I had an electrician come in and install a new sub panel in my house and wire up my kitchen. When he finished, I took it from there. Now that I have the rest of the house wired, its time to connect it all to the sub panel. Both the neutral bus bar and the ground bus bar (2 separate buses) seem to...

Hot neutral Wires [ 6 Answers ]

The wife turned on the toaster this morning and the thing quit and the receptacle was melted a bit,the breaker never tripped, fridges outlet does not work along with two in the living room. I replaced the melted receptacle. Still nothing on all four outlets the NEUTRAL reads 120 volts with ground...

Open neutral - 3 wires; white as hot? [ 1 Answers ]

OK, I've encountered an oddly wired outlet in my kitchen and am trying to replace it with a GFCI. I unwired the old outlet, taking note of where things were attached, just in case. I wired the GFCI acoording to instructions and then checked the wiring with a Sperry GFI checker. All seemed OK. ...


View more questions Search