    jasv's Avatar
    jasv Posts: 35, Reputation: 2
    Junior Member
     
    #1

    May 4, 2005, 03:07 PM
    Motion sensors on 3 way switch
    First I apologize for my terminology. I have a switch a the bottom of the stairs and one at the top of the stairs. They both control the same light fixture. I think this is called a 3 way switch?

    My real question: I bought 2 levition motion switches that state they work with 3 way switches. The example shows how to wire one motion sensor to one switch. What I would like to do is put a motion sensor both at the top and the bottom of the stairs. That is replace the 2 existing switches with 2 motion sensor switches. Any reason whay that wouldn't work?
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    May 4, 2005, 05:03 PM
    Can you furnish the Leviton model number of the switches you have? Leviton makes several models for 3 way switches,and each is wire differently, as I can see from the spec sheets at their website.

    You can try:
    http://www.leviton.com/sections/prod...d/npleadin.htm, and chose "Occ. Sensors" on the left pane, and find you sensor.

    To find your model number and read the wiring diagrams there for 3 way arrangements.

    Otherwise get back with the number and I can see how it needs to be connected and help you.

    By the way Leviton also offers live tech support "In the US 1-800-824-3005
    Mon.-Fri. 8:30AM to 6:00PM ET". I have used it several times myself in the past and they are very helpful.
    labman's Avatar
    labman Posts: 10,580, Reputation: 551
    Uber Member
     
    #3

    May 4, 2005, 05:20 PM
    Yeah, that is what is called a 3 way switch. Both the switches, regular or motion sensor, must be double throw, common, normally open, and normally closed. If your example shows the motion sensor switch with 3 contacts to connect to the black, white, and red wires, doing so with both switches should work. If your example shows a single throw motion sensor switch connected to the black wire of the feed pair, 2 of them are not going to work. It is possible that one motion sensor might detect motion at both the top and bottom of the stairs, needing only one switch.

    There are several ways of wiring up 3 way switches. You have a pair of feed wires going to either one of the switches or the load. Then the rest are connected by 3 conductor cables. When you remove the old switch, carefully note how the wires are connected, and connect the new wires just like them.
    jasv's Avatar
    jasv Posts: 35, Reputation: 2
    Junior Member
     
    #4

    May 4, 2005, 07:08 PM
    3 Way motion sensor
    Tkrussell,
    The model number is PR180-1LW. The wiring diagram shows an example of a 3-way installation with the PR180 to a standard 3 way switch.

    Labman,
    If your example shows the motion sensor switch with 3 contacts to connect to the black, white, and red wires, doing so with both switches should work. If your example shows a single throw motion sensor switch connected to the black wire of the feed pair, 2 of them are not going to work
    The example shows the black wire of the feed pair connected to the black of both the swtich and the PR180 utilizing a "jumper".

    I will try your "one motion sensor" idea because that might work. Thanks.
    KPark214's Avatar
    KPark214 Posts: 1, Reputation: 1
    New Member
     
    #5

    Oct 11, 2005, 07:24 AM
    Same switch deal
    But I want to know how to install this same switch with only a single pole operation. I have tried pretty much every combination there is and this still does not work. Please help me out. Plus would like to also know howto fit this into the box because it doesn't quite fit.
    labman's Avatar
    labman Posts: 10,580, Reputation: 551
    Uber Member
     
    #6

    Oct 11, 2005, 10:16 AM
    Any double throw switch should work as a single throw one too. You need a hot wire, and a wire connected to the load. The other side of the load must be connected to a neutral running back to the breaker box. From there, it is simply making sure one of the wires is connected to the common of the switch. Your problem may have to do with the connections at the other old switch. Be best to identify which wires need to be connected there, wire nut them together, and cap off all unused wires. Remove the other switch, and put a blank cover over the box. Code requires it to remain accessible as long as the wiring in it is in use.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Motion Sensing Wall Switch causes flickering lights [ 4 Answers ]

I just bought a Cooper Motion sensing wall switch. I wired it (correctly?) and I am getting flickering lights when the switch automatically turns itself off. I have good lights in the "on" positions, and when I turn the lights off there is no flicker. However, when the "motion" stops, the light...

Need motion in opposition to defendants motion for summary judgement & TO STOP Thief [ 5 Answers ]

Good day all,received a motion in the mail "plaintiff's motion for default judgement as to defendents xxxxxx,xxxxxx,xxxxxx, and judgement on the pledings as to defendant xxxxxxx (state gov agency that sold the tax deed ) this case is about a overlooked tax lein sold against my grandmothers house ...

Questions on wiring up a Leviton PR180 Motion Activated Switch [ 1 Answers ]

Newbie here - hopefully you guys can give me some help on a wiring question. I have two boxes - box 1, which is where I would like to put the PR180, has the following wires: Hot, Traveler A and Traveler B. Box 2, which is where the normal 3-way switch is, has Traveler A, Traveler B and what I...

Replace 3 way switch with motion 3 way [ 7 Answers ]

Hi I have a 3 way switch setup today that works and I now want to replace one of the switches with a motion sensor. I purchased the Levition PR180 to do the job. (at least it says is can). The setup I have current is 1st box - power comes in Light fixture is attached ...


View more questions Search