Mixing Wire Gauges

Asked Aug 3, 2008, 11:15 AM — 13 Answers
Hello,

I have a microwave oven which I am going to need to hardwire. The circuit (dedicated) is 12 awg and the breaker is 20amp. The power cord of the oven is 14 awg and the output is 1.58KW (13A, yes?). Will I be allowed to connect the power cord of the oven to the 12 gauge wire?

Thank you

13 Answers
KISS's Avatar
KISS Posts: 12,602, Reputation: 4378
Uber Member
 
#2

Aug 3, 2008, 11:22 AM
Yes, because the microwave has an internal fuse.
Helpful
stanfortyman's Avatar
stanfortyman Posts: 4,891, Reputation: 1331
Electrical & Lighting Expert
 
#3

Aug 3, 2008, 11:41 AM


Also, the power cord has nothing to do with the branch circuit. You are NOT mixing wire sizes.
Helpful
tkrussell's Avatar
tkrussell Posts: 9,673, Reputation: 3698
Senior Electrical & Lighting Expert
 
#4

Aug 3, 2008, 12:12 PM


Well, you have two positive answers, how about one negative.

Does the manufacturers instructions explain that this unit can be "hardwired" using the cord? I doubt it.

My interpretation of hardwire would be the #12-2 cable connecting to directly to the unit, which may or may not be allowed with your unit.

If you cut the male plug end off the cord, and splice it onto the #12 cable, this will violate the UL listing of the unit, and violate the electric code by including cord into the system.

Cutting off the male plug also eliminates the required service disconnect the plug and outlet offered.

Why do you feel it is necessary to hardwire this unit? You can drill a hole in a cabinet to allow the cord to pass through to where the outlet is located.
Helpful  (1)
stanfortyman's Avatar
stanfortyman Posts: 4,891, Reputation: 1331
Electrical & Lighting Expert
 
#5

Aug 3, 2008, 12:29 PM


Wow. I totally missed the word "hardwire".

TK is completely correct on this.
Helpful
Washington1's Avatar
Washington1 Posts: 800, Reputation: 187
Senior Member
 
#6

Aug 3, 2008, 12:40 PM
Never seen a stand alone micro hardwired.
Helpful
stanfortyman's Avatar
stanfortyman Posts: 4,891, Reputation: 1331
Electrical & Lighting Expert
 
#7

Aug 3, 2008, 12:54 PM
I am also VERY curious (and skeptical) as to why is HAS to be hardwired?
Helpful
KISS's Avatar
KISS Posts: 12,602, Reputation: 4378
Uber Member
 
#8

Aug 3, 2008, 03:08 PM
Me Too! Missed the hardwired. Good catch.
Helpful
magicalpig's Avatar
magicalpig Posts: 4, Reputation: 1
New Member
 
#9

Aug 4, 2008, 08:25 AM
Stanfortyman, you are justified in your skepticism: it doesn't HAVE to be hardwired. I am trying to minimize the amount of wall tearing I'll have to do because of a mistake in my initial design. I thought I could get away with not having to drill through the bottom of the cabinet and instead plug into a recessed, wall clock outlet directly behind the mwave. When I got down to business after already having installed said outlet in new construction fashion, I saw that the plug was too long to fit in the recessed outlet and would push the microwave away from the wall. I considered splicing a different style plug onto the cord, but I still had another problem: the cord which exits from the top of the microwave was too thick to route between the unit and the upper cabinets and then down the back of the unit to where the outlet was. I was now considering modifying the microwave so the cord exited from the back. At this point I realized what a big mess I was in just to avoid drilling into my cabinets.

The proper way to fix this (I think) would be to remove the recessed outlet and splice some more romex into that location. Run the romex higher up the wall to a spot behind the cabinet and terminate it at a new 15-amp receptacle which will be accessed through a cutout in the back of the cabinet.

Last night, I didn't quite follow that prescription. I ran the extra romex to behind the cabinet, but I didn't wire in a receptacle -- I was still planning on hardwiring -- but this was before I read everyone's responses here today.

Tkrussel, I don't at all doubt what you're saying, but I just don't understand why the UL Listing and electrical code will be violated if I do this. Can you explain why please?

Thanks everybody
Helpful
tkrussell's Avatar
tkrussell Posts: 9,673, Reputation: 3698
Senior Electrical & Lighting Expert
 
#10

Aug 4, 2008, 05:02 PM
Rather than me try to explain the listing, read this from Underwriters Laboratories to get you started:

UL | Field Modifications

As far as the code issue, hard to show that since what you proposed is not allowed nor addressed in the electric code by any language in so many words that an appliance can be hardwired by cord,

However,
Section 110.3(B) of the NEC states:

Installation and Use
Listed or labeled equipment shall be installed and in accordance with any instructions included in the listing or labeling.


Any AHJ, AKA inspector, will cite this section and have UL behind him to redtag the installation.

What is worse is an inspector hired by your insurance carrier , eh um...., that is knowledgeable about this issue, after any claim has been made.

Also remember there is the service disconnect issue. It's been busy and I am tired, don't make me go find that code too. Hopefully someone can back me up here.

This is an easy catch for any inspector, as many are getting more stringent with UL compliance.

Sure it is a technicality of sorts, but rules are rules,better wording is Standards.

Chances of anything happening is probably slim to none, but that cannot be my official advice. While there is no formal oath electricians take to become one, that I know of, there is professional ethics we volunteer to follow, other than the legal verbage in the state statutes that govern the license we are issued.

Now that I think, I do remember raising my hand while applying for a permit in New Haven, first time I was ever asked. I said "Really?", and he said yep, and every city or town can, and should require an electrician to swear to follow all applicable codes.

So I guess I do recall taking an oath. Anyone else ever run into that?

Do what ever you need to pass the cord through the cabinets to an outlet that can be in any cabinet nearby.

I hope this helped.
Helpful

Not your question? Ask your question View similar questions

 
Thread Tools Search this Thread
Search this Thread:

Advanced Search

Add your answer here.

Remove Text Formatting

Undo
Redo
 
Decrease Size
Increase Size
Bold
Italic
Underline
Align Left
Align Center
Align Right
Ordered List
Unordered List
Decrease Indent
Increase Indent
Insert Email Link
Wrap [QUOTE] tags around selected text
Wrap [CODE] tags around selected text
Wrap [HTML] tags around selected text
Wrap [PHP] tags around selected text
Wrap [YOUTUBE] tags around selected text
Notification Type:



Check out some similar questions!

Mixing old and new wire [ 8 Answers ]

Live in a circa 1940's home with old non-grounded NM cable, cloth outer shell, insulated wires. There are currently 14 outlets on 1 circuit, in addition to 5 ceiling lights. Obviously the circuit is overloaded. I'm planning on running 3 new circuits (living room, bedroom, dining room are...

Screwball gauges. [ 1 Answers ]

This guy in a peircing shop put in screwball gauges in my ear. He said in one month you can change them. So today I tried changing them but they wouldn't come out I literally tried for two hours to unscrew them from my ear. How do I unscrew the screwball gauges and take them out?!

Mixing gauges - variation on a theme [ 3 Answers ]

I've seen similar posts, but not similar enough to make me feel 100% sure so here we go... Once upon a time there was a hot tub on the back patio of my house. The wire appears to be 4 gauge wire and there is a junction box already installed on the back wall. The tub is gone now, and I'm...

Mixing wiring and outlet wire gauge . [ 5 Answers ]

If I have a 15 amp circuit, and 14 gauge wire, why can't I install a 20-amp outlet? If a 20-amp device is plugged into the outlet, won't the circuit trip, preventing overload? Also, 20-amp outlets and 15-amp outlets appear to have the same connection for devices (two prongs and a ground hole),...


View more Electrical & Lighting questions Search