    Meter Base with disconnect and A/C Breakers
    My meter base will have an outside 200amp disconnect. It will also have three 30amp breakers to feed the A/C units located a few feet from the meter. There will also be a 200amp main panel located in the basement.

    My question is if my disconnect outside is a 200amp and I have three 30amp breakers for the A/C units, will it be fine to have a 200amp main panel inside. Or should it be smaller since there are three 30amp breakers outside. There has been a survey done using total estimated amp usage that included all major appliances, A/C & Heat units, square footage etc. and it showed that we will be at about 147amps total.

    Another question that I have is about the 30amp breakers outside. From what I understand, they will be the thinner space breakers to allow for room to fit three of them in the slots. The electrician said that they will be double throw. Is this OK?

    Thanks...
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Feb 14, 2007, 03:39 AM
    Having the 200 amp panel inside is fine, along with the 3 - 30 amp breakers outside for the HVAC units. All of this is protected by the 200 amp main disconnect outside.

    Are you sure the HVAC breakers are "double throw" and not double pole? The HVAC units will be 240 volt rated, and need 2 pole, or "double pole" circuit breakers.

    Is the outdoor meter some sort of combination meter/panellboard with a main breaker and space for branch circuits?
    Hoot01's Avatar
    Hoot01 Posts: 15, Reputation: 1
    New Member
     
    #3

    Feb 14, 2007, 11:51 AM
    Yes tkrussell... You are correct... they are double pole. These will feed 240 volt 25 amp units. The outdoor meter is a GE Combo unit. It has the meter base with a separate section below it that will house the 200 amp main and the 30amp breakers. Will the thin type breakers be OK?
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #4

    Feb 14, 2007, 02:00 PM
    The thin, or half size as GE calls them, will work just fine, as long as the panelboard can accept them, which I assume the electrician already knows they will fit.

Not your question? Ask your question View similar questions

 

Add your answer here.


Check out some similar questions!

Gold base and blue base hair color [ 2 Answers ]

I have many times colored my hair in years past. I always used miss clairols blondest beige and it always turned out fine. About 4 years ago I grew it all out my natural color. Light light brown (dishwater blonde) Anyway.. last night.. I decided to color my hair I bought lightest golden blonde...

Loud Buzzer-Must Disconnect! [ 1 Answers ]

I have a one year old Kenmore stacked washer/dryer. Our house is small and the buzzer is too loud, I can here the dryer stop by itself. How can I disconnect it? Thanks!

Another disconnect question. [ 5 Answers ]

Greetings all... I've spent the last few minutes reading several questions about main disconnect panels/breakers outside the home ( between the meter and breaker box ). I had been thinking about inquiring about having such a device installed here in my NC home. You see, my house is very old,...

Want to auto disconnect AOL [ 2 Answers ]

Hi: I'm running XP and AOL9 w/ dial-up. Is there some way I can configure AOL to automatically disconnect? I've accidentally left my computer connected for hours and upon my return AOL is still running. I thought to use parental controls but this only works for 1 screen name at a time. I...

Hot Tub Disconnect [ 4 Answers ]

From reading past questions and responses, I got a fairly clear idea about how to wire the GFI panel between the distribution panel and hot tub. Thanks for the references that people posted! There is still one requirement, however, that still puzzles me. The NEC calls for a disconnect to be...


View more questions Search