    dwright30's Avatar
    dwright30 Posts: 2, Reputation: 1
    New Member
     
    #1

    Feb 18, 2007, 06:44 AM
    Main panel as subpanel
    Hello: I stumbled across your forum and found a question that was close to mine, but have a more detailed query. I am wiring a shop/apartment. The building has a 200 amp service panel. The main loads (a/c, range) and dedicated loads (fridge, smoke detectors, etc) are branch circuits on the main service panel. I purchased a 125 panel at home depot (it looks like a main panel because it has a 125 amp breaker at the top). I put a 100 amp breaker in the main panel and connected the two panels using #2 copper. The two wires from the 200 amp main panel go to the 125 amp panel in the sub-panel. A #2 wire connects the main neutral bus to the sub neutral bus. I installed a separate ground bus in the sub panel, bonding it to the sub panel using machine screws; the ground bus is connected to the main panel's neutral/ground bus using #2 copper.

    I wired a number of branch circuits into the shop/apt from the subpanel. My concern is in knowing that the sub panel's neutral bus is not bonded to the box. I have looked at the box (a GE 125 amp, 24 circuit load center) and I don't see any obvious connections that would bond the neutral bus to the box. I did not disconnect anything that would have bonded the neutral to the box. Does this sound reasonable? My logic is that is is unlikely that the neutral bus would be bonded to the box by default, but I am looking for some reassurance that my thinking is valid. As I am looking for a safe installation, any advice would be deeply appreciated.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Feb 18, 2007, 07:03 AM
    The neutral in a subpanel is not to be bonded to the metal box, or equipment ground. So sounds like you did exactly as should be done.

    The neutral and equipment ground only gets bonded at the location of the Main Service Disconnect, which sounds like your Main Panel.
    dwright30's Avatar
    dwright30 Posts: 2, Reputation: 1
    New Member
     
    #3

    Feb 19, 2007, 06:37 PM
    Thanks for the response. It puts my mind at rest as I continue the project. I have read your other responses and they sound very good and are not condescending.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Difference between Main Lug and Main Breaker Panel [ 8 Answers ]

What is the difference between a Main Breaker Panel and a Main Lug Panel and can either be used in new residential construction.

Making the house panel a subpanel [ 2 Answers ]

The question involves a house with a detached garage that is about 60' away. The feed from the utility spans a considerable distance, whips in the wind and is near trees. The owner wants a subpanel in the garage for hobby activity. The utility has suggested relocating the man incoming line...

Subpanel or main service panel? [ 4 Answers ]

Hello, I want to put a subpanel in my shop, and was wondering if a main service panel that they sell at say Home Depot is the same thing as a subpanel? I have a 200 amp service to my house, and want to put a 100 amp subpanel in my shop. Does the term "subpanel" just mean that it is wired off the...

Putting a subpanel side by side with a main panel [ 1 Answers ]

Hello, I am looking to put a subpanel side by side with a main panel. The sub panel will be connected to the main by a 1 & 1/2 inch metal conduit since the two panels will be electrically connected by the conduit - do I still need to separete the neutral and ground bus? Thanks, Martin

Large subpanel off a 200 amp main [ 9 Answers ]

I'm trying to replace an older subpanel in a barn 200' from the main 200 amp panel. I have many questions; How can I get a 200 amp rated panel out in the barn, what kind of tap/connection would I have to use coming off 200 amp main, what size conductor would I need, is this even allowed by NEC?


View more questions Search