    Main panel and sub panel breakers
    I inspected a sub panel fed with a number 4 copper cable. The main panel breaker was a 90 amp breaker, but the sub panel breaker was a 100 amp breaker. Is this OK?
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Jun 23, 2007, 12:53 PM
    Sure, a bit odd , but the 100 amp cable and downstream breaker is now protected at 90 amps. Any overload at the sub panel will cause the 90 amp Cb to trip, while the 100 amp Cb will remain closed.

    #4 copper is allowed by NEC code as a 100 amp residential only feeder.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Difference between Main Lug and Main Breaker Panel [ 8 Answers ]

What is the difference between a Main Breaker Panel and a Main Lug Panel and can either be used in new residential construction.

Main Panel to Sub Panel [ 2 Answers ]

I currently have a CH MBE4040B200BTS Meter main panel on my pump house drawing only power to run booster and well pumps, here is what I wish to do: Add a CH BRS225 (feed thru) to a CH BR4040B200 Main Breaker sub panel for my shop. Both panels are only 200 amp service, I will not be running more...

60 Amp Panel.how many breakers? [ 2 Answers ]

I recently bought a house with an old Federal Pacific Panel in it. (Yes yes I know, major fire hazard.) I was just wondering, it is rated as a 60 amp panel, does that mean that the sum of all the breakers must be less than 60 amps, or that no one breaker can exceed 60 amps?

Main Circuit Panel to Branch Panel? [ 1 Answers ]

Hello experts, OK... My Main Load center in my home has a branch circuit connected to a 60 amp breaker. The branch feed wire is a 4awg copper wire. The branch panel is downstairs and it has a 100amp main cutoff breaker installed in it. It feeds the whole downstairs including... (1)...

200 Amp Service Panel with 60 Amp Main Breakers [ 26 Answers ]

I was told when we purchased our house that it had 200 Amp service which it appears to be; however, the top of each bus bars only has 60 Amp breakers for the Main shut offs. Is this normal? Each bus bar is connected to a hot wire (one red and one black) and then the two 60 amp breakers are...


View more questions Search