    Main breaker flips off before lesser breakers go
    My problem is the main breaker in the house will flip off before any of the smaller specific breakers flip off. Something is getting overloaded but the smaller breakers are not taking the load.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Apr 3, 2007, 02:45 AM
    I don't think you have an overload, more that the main breaker is defective, or thee is a loose connection on the Line or Load of the breaker, causing heat, which is migrating into the breaker, causing a false trip.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Difference between Main Lug and Main Breaker Panel [ 8 Answers ]

What is the difference between a Main Breaker Panel and a Main Lug Panel and can either be used in new residential construction.

New 15A breaker trips main 100A breaker [ 6 Answers ]

Hi, I've been finishing my basement and I added a few 15A breakers One room has 8 outlets in series with the first starting about 6 feet from the main panel. There is currently no load on this outlets. When installing the drywall I accidentally shorted the outlet closest to the panel. It...

A/c popping main breaker [ 4 Answers ]

We purchased a reconditioned unit to replace an older unit in a mobile home. The unit worked in the shop where we purchased it. We hooked up the 2 110V lines and then turned on the thermostat to cool. Immediately following, the main 100 amp breaker popped. We then disconnected the thermostat wires...

Breaker Box Amps rating & Number of breakers installed [ 1 Answers ]

I have a question in regards to amps allowed in a breaker box. My breaker box has a label stating that the box has a maximum load of 200 amps, but that it is convertible. I really don't know what the convertible part means. If I look at the breakers installed, these add way more than 200 amps. ...

Main breaker and main disconnect [ 2 Answers ]

What I have is a home built in 1960 moved in 2 years it had a meter hanging from the rear of house with no main, 240v 50amp circuit to stove, 240 30amp to dryer, 5 breakers for the rest of house 1 20amp and 4 15amp. What my plan is to replace the meter housing and put a g.e. 200amp Disconnect on...


View more questions Search