Home > Home & Garden > Electrical & Lighting   »   Load panel capacity 200 amp

 
Question Tools Search this Question Display Modes
Question
 
 
#1  
Old Mar 4, 2007, 07:16 AM
doug196
New Member
doug196 is offline
 
Join Date: Mar 2007
Posts: 1
doug196 See this member's comment history on his/her Profile page.
Load panel capacity 200 amp

I have a challenger load panel SB20 (20-40) CT. Which is a 200 amp panel.

The number of switches currently in the panel are 19 total. Total amp of all switches is 360. Some of those circuits are dedicated to a sole source. GFCI to Whirlpool tub for example.

This panel has 20 1" spots available but 1/2" breakers can be used according to panel.

The problem is although 200 amp service and code says no more than 42 switches which we are well within, the panels states that the sum of circuit breaker ratings not to exceed 125 amps per branch bus stab.

Why would a 200 amp box limit to a total of 250 amps total amps when not all the electricity is being used at the same time? Was it just to cya if someone went overboard? Also would I being against code to exceed what the manufacturer has written on the panel sticker?

This will be an extremely expensive upgrade to just switch out panels as I see.

Reply With Quote
 
     

Answers
 
 
Old Mar 4, 2007, 07:50 AM   #2  
nmwirez
Full Member
nmwirez is offline
 
Join Date: Feb 2007
Posts: 446
nmwirez See this member's comment history on his/her Profile page.
Quote:
Originally Posted by doug196
I have a challenger load panel SB20 (20-40) CT. Which is a 200 amp panel.

The number of switches currently in the panel are 19 total. Total amp of all switches is 360. Some of those circuits are dedicated to a sole source. GFCI to Whirlpool tub for example.

This panel has 20 1" spots available but 1/2" breakers can be used according to panel.

The problem is although 200 amp service and code says no more than 42 switches which we are well within, the panels states that the sum of circuit breaker ratings not to exceed 125 amps per branch bus stab.

Why would a 200 amp box limit to a total of 250 amps total amps when not all the electricity is being used at the same time? Was it just to cya if someone went overboard? Also would I being against code to exceed what the manufacturer has written on the panel sticker?

This will be an extremely expensive upgrade to just switch out panels as I see.
NEC 220 load calculations allow demand factoring for branch circuit loads for determining the 200/225 amp panel rating qualifications for residential service sizing. Adding up all the breaker ampacities in the panelboard is not an actual condition of the panel capacity demand loading. Some circuits are continuous, some are not, so looking into code requirements (I.e. Table 220.54 and 220.55 factor charts for a start) will help you on this matter that really takes a bit of explaining. nm
  Reply With Quote
 
     


Question Tools Search this Question
Search this Question:

Advanced Search
Display Modes

 
Similar Sponsors

Similar Questions
Question Asker Topic Answers Last Post
Load Center Capacity needhelp-2 Electrical & Lighting 4 Today 06:02 AM
200 amp panel feeding a 100 amp panel roughly 130' away tdude12181 Electrical & Lighting 3 Mar 23, 2008 06:14 AM
200 amp main service panel M21519 Electrical & Lighting 1 Feb 23, 2007 04:40 AM
runing 100 amp sevice panal 200 ft away from main 200 amp service jpriest6523 Electrical & Lighting 1 Feb 5, 2007 12:49 AM
size of 200 amp panel box brianac27 Electrical & Lighting 2 Jan 8, 2007 03:48 AM




Copyright ©2003 - 2007, Ask Me Help Desk.
All times are GMT -8. The time now is 11:31 AM.

Content Relevant URLs by vBSEO 3.0.0 RC6 © 2006, Crawlability, Inc.