Light switch issue, Light stays on!

Asked Aug 7, 2007, 05:39 AM — 8 Answers
I'm having a problem with a light switch...the light stays on regardless of the position of the switch. I have swaped the switch out with a new one and still have the same problem. The switch controls to recessed lights over a fireplace.

In the box on the wall there are several wires:
2 white wires that are capped off. Neither gives any voltage reading
2 black wire capped and tied with a lead that goes to the switch. On of the original black wires gives a constant 120v, the other is 0, obviously the lead is giving a constant 120v.
One red wire that gives a constant 120v, this was conncected to the other position on the switch
A ground wire that was connected to the switch

What is more strange is that if I separate all the wires that are capped off together together, take out the switch so that no one wire is touching another, when I flip the breaker back on, the light still goes on!

Please help,

Thank you

8 Answers
Stratmando's Avatar
Stratmando Posts: 10,435, Reputation: 2520
Uber Member
 
#2

Aug 7, 2007, 05:55 AM
Did you change any recepticles? If so may be a tab on hot side of receptacle that needs to be removed.
Helpful
ebaines's Avatar
ebaines Posts: 10,055, Reputation: 5539
Expert
 
#3

Aug 7, 2007, 07:03 AM
Is this a new problem, or did it just start happening recently, perhaps after someone did some work on the recessed light fixture? It may be that the wiring in the recessed fixture is hosed up - check to see if there is a black wire up there that is wired to the hot lead of the fixture, instead of the other end of that red wire you mentioned being wired to the fixture as it should be.
Helpful
cdehrlich's Avatar
cdehrlich Posts: 5, Reputation: 1
New Member
 
#4

Aug 7, 2007, 08:17 AM
Quote:
Originally Posted by jmat1980
Im having a problem with a light switch...the light stays on regardless of the position of the switch. I have swaped the switch out with a new one and still have the same problem. The switch controls to recessed lights over a fireplace.

In the box on the wall there are several wires:
2 white wires that are capped off. Neither gives any voltage reading
2 black wire capped and tied with a lead that goes to the switch. On of the original black wires gives a constant 120v, the other is 0, obviously the lead is giving a constant 120v.
One red wire that gives a constant 120v, this was conncected to the other position on the switch
A ground wire that was connected to the switch

What is more strange is that if I separate all the wires that are capped off together together, take out the switch so that no one wire is touching another, when I flip the breaker back on, the light still goes on!

Please help,

Thank you
It sounds to me like the switch that you THINK controls these lights does not -- but actually controls something else. Have you searched for an additional switch someplace?
Helpful
jmat1980's Avatar
jmat1980 Posts: 2, Reputation: 1
New Member
 
#5

Aug 7, 2007, 08:50 AM
The switch used to work, I tried (unsuccesfully) to install a dimmer and when I put the reg. Switch back on is when the problems started. The wires up at the fixture have not been messed with at all...
Helpful
ebaines's Avatar
ebaines Posts: 10,055, Reputation: 5539
Expert
 
#6

Aug 7, 2007, 09:09 AM
Just reread your original post - you say that you have two leads in the switch box that are constant 120 volt - one of the blacks and the red, correct? Connecting both of these leads to the switch wouldn't do any good at all if they're both permanently hot. Could it be that the red lead was rewired somehow, perhaps at another receptacle? Also, open up the light fixture and tell us what leads are there, and how they're connected.

Also, please confirm that the lihght is on a simple 2-way switch circuit, and not a 3-way.
Helpful
carliz777's Avatar
carliz777 Posts: 1, Reputation: 1
New Member
 
#7

Apr 4, 2012, 08:01 AM
I simply replaced the light switch that the hot and neutral wires are attached to and it worked fine. Those switches burn out sometime I guess.
Helpful
Stratmando's Avatar
Stratmando Posts: 10,435, Reputation: 2520
Uber Member
 
#8

Apr 4, 2012, 02:21 PM
carliz777, You do not want to have a hot and neutral connected to a Singlepole switch, Unless you want maybe see if a Breaker will trip, Turn on switch and if the Breaker Trips, the Breaker is good.
Helpful
ma0641's Avatar
ma0641 Posts: 6,253, Reputation: 2494
Plumbing Expert
 
#9

Apr 5, 2012, 02:12 PM
With a black and red on the switch, you appear to have a 3 way. Isn't there another switch? Does the switch say ON and OFF or is it blank?.
Helpful

Not your question? Ask your question View similar questions

 
Thread Tools Search this Thread
Search this Thread:

Advanced Search

Add your answer here.

Remove Text Formatting

Undo
Redo
 
Decrease Size
Increase Size
Bold
Italic
Underline
Align Left
Align Center
Align Right
Ordered List
Unordered List
Decrease Indent
Increase Indent
Insert Email Link
Wrap [QUOTE] tags around selected text
Wrap [CODE] tags around selected text
Wrap [HTML] tags around selected text
Wrap [PHP] tags around selected text
Wrap [YOUTUBE] tags around selected text
Notification Type:



Check out some similar questions!

No Blowing/Aux Light Stays On [ 1 Answers ]

My first post. Hello everybody! I have a Trane XB80 gas furnace - appox 5years old. The thermostat is set on 80 but the thermostat's thermometer shows about 60 in my cold room. The green aux light stays on until I move the thermostat to about 60. I notice today that - what I guess is - the...

Light switch hot then light went off [ 1 Answers ]

We have a standard ugly flourescent overhead fixture in the kitchen. This morning the light just went off. I went to see if the bulb had burned out and the light switch itself was hot. What could cause this? I had not noticed the switch ever getting hot before. It wasn't really super hot but...

One Switch two lights - the second light furthest away from light won't turn off [ 4 Answers ]

One Switch two lights - the second light furthest away from light won't turn off but the first one does Worked until I swopped the roses. Suspect that didn't do something right when putting them back. Up to now - left bulb out but need to get it to work now.

Light switch won't control light [ 2 Answers ]

I took down a ceiling fan and connected a new chandelier. Very basic white from light to white in ceiling, black from light to black from ceiling, ground to ground. There is also a pink wire from ceiling that I just capped. when I turned the fuse back on the light came on but the wall switches...

Light and switch issue [ 3 Answers ]

I am attempting to replace an existing light fixture. I have discovered four wires coming into the opening. When I connect the new light *** the old one was I only have power before the light and the new light comes on. No power to the rooms beyond the light. In addition, the new light is on...


View more Electrical & Lighting questions Search