 | | | That intersting--60 amp sub-panel #4 or #6 wire.
Asked Jun 4, 2008, 05:48 PM
—
21 Answers I am getting mixed messages from different licenced electricians. Run length 100ft. 60 amp sub-panel in 1" conduit. Wire size according to NEC?
2 electricians have stated #6
1 electrician has stated #4
I have also verbally talked with another electrician that said you have to rate the wire based at 60deg not 90deg because the breaker says 60deg and that is the weakest link
I am starting to get confused. I don't get why there is grey in the above picture. At 1st I was thinking voltage drop, but after looking into it further this should not be a problem.
Any feedback would be good.
Chuck Thread Summary |
21 Answers
 | Uber Member | |
Jun 4, 2008, 07:43 PM
| | | That 60 Amp subpanel is going to have a hard time fitting inside a 1" conduit. <G>.
I believe you mentioned a lot of motor loads, but I'm not sure. Motor loads may increase requirements.
Are we talking apples (copper) or oranges (Aluminum)?
What is the continuous load (multiply amps by 1.25) (on for more than 3 hrs) and non-continuous loads?
Type of wire?
Did you do voltage drop calcs based on 240 or 120 V? The sizing to the box should be based on 120V and 3 wires, even though it's 240 and 4 wires.
There is lots of grey. | | |  | New Member | |
Jun 4, 2008, 09:05 PM
| | | You are correct about he Grey. I apologize for that. Let me clarify this a bit better---
This would be for a wood work shop. Most of the major draw will be for 30 minutes or less.
->The biggest draw I see at one time would be-- 24 amps 5hp motor---220
18 amps-3hp motor--220
8 amps---120 Continuous
10 amps--120 Continuous
->All the wire I would be using is copper--thhn
->I was planning on 1" EMT for the raceway
->Main Box 200amp Bryant
->Planned sub-panel Square D
I think that should help see things a little bit better I was under the impression that 4(2 black, 1 white, 1 green) #6 thhn was fine in 1" EMT. Am I missing something here? | | |  | Uber Member | |
Jun 4, 2008, 10:51 PM
| | | Let's do voltage drop calculations backwards:
60 A breaker, means 48 Amps continuous (Maximize service), 100' away
#6 Cu would yield 3.9% drop at 120 V and 48A
# 4 Cu would yield 2.5% drop at 120 V and 48 A
OK, now for some intuative stuff because of the 120 stuff.
It could be a) 24+18+8+10 or 60 amps or it could be:
b) 24+18+2 or 48 Amps depending on how things are wired.
If the loads were calculated, you would end up as (24+18)+(8+10)*1.25 or a circuit rating of 63.6 and you would have to round up to the next breaker size.
You could sustain 60A without tripping, but you have a continuous load of 18 A derated by multiplying by 1.25.
In b, you would have a circuit of (24+18)+(2*1.25) or 44.5 A, you would have to round up to a 50 A breaker.
You probably want to keep the drops to within 3% especially because of the motor loads. There will be a starting current. I see you did use FLA (Full Load Amps). In the US, there isn't 220 V anymore. It's 240/120. Continuous loads are multiplied by 1.25 to get the OCPD (Overcurrent Protection Device). 120 volt loads can be carried as the sum or the difference depending on if they are distributed between the hots. Doing the voltage drop calculations based on 240V seems to be a mistake people make. Now when sizing wire to the 240 V motors, you would use 240 V because there is no neutral to the equipment. The neutral carries the difference of the currents on the hots.
My vote is for #4 Cu with the two 120 V circuits split - One on L1 and 1 on L2. | | |  | New Member | |
Jun 5, 2008, 12:23 AM
| | | KeepItSimpleStupid: Wow, then out of the 3 licenced electricians only one was right. That is kind of of scary. It will be interesting to see what the 4th electrician says, as I have a final quote tommorrow.
Two final questions-- What size emt would I use for #6? What size emt would I use for #4?
So far all quotes have included 1". But the one who quoted #4 also said 1".
I think 1" is fine for #6, but for #4 it would be tight and out of code. Am I correct. I didn't say anything to the electrcian because I am not one to tell someone how to do there job.
Last question--Off the subject, but I have always wanted to know--When can the plastic conduit be use in place of EMT? I always have believed that plastic was used only for underground, but when at HD the clerk said people use it in attic all the time and it is fine. I couldn't debate his statment because I am not familiar with the plastic. I think there are 2 types, but I am not even sure on that. Anyway, a few quick comment on plastic would be helpful for me to know. Type and Usages?
Thanks a lot for your feedback. I think I will use the electrian who is using #4. | | |  | Uber Member | |
Jun 5, 2008, 07:35 AM
| | | For #4's won't fit in 1 EMT, but the ground conductor can be smaller, so therefore it COULD be OK with a smaller gage ground wire.
1-1/4" EMT will fit four #4's or 4 #6's.
I'll refer you here: Electrical Wiring in the Home: Wire Size for Subpanel, amp breaker, gfi outlet
Conduits:
There are a number of types such as EMT, ENT, IMC, LFNC, RMC, PVC and HDPE
With the plastic conduits, the wall is thicker and therefore less wire can be run in the space. So, there is a disadvantage. You can't disassemble them. They are inherently water tight.
You have flexible conduits which can be watertight.
And you have rigid and non-ridged conduits.
So, the bottom line is you have to use plastic conduits underground and for above ground applications you might have to bump up the size compared to EMT.
1" EMT may be OK with 3 ea #6 and 1 ea #?, which would be a smaller ground conductor which is permissable. I did not determine the ground size.
Grounds handle fault currents and therefore do not have to sized as the current carrying conductors. Take a look at the ground wire in a standard 14-2 w/ground Romex or NM-B cable. | | |  | Uber Member | |
Jun 5, 2008, 07:45 AM
| | | Here is some info on PVC and HDPE matherials: Thermoplastics | | |  | New Member | |
Jun 5, 2008, 08:07 AM
| | | KeepItSmpleStupid--Question about something I have never heard of in one of the abover links. Electrical Wiring in the Home: Wire Size for Subpanel, amp breaker, gfi outlet Also a relatively new code requirement, when installing a subpanel you have to use the fourth ground wire, in this case the #8, and also drive a ground rod and bond it to the ground bar of the sub panel.
I understand ground rod because this is not an attached garage. But what I don't get is the extra ground wire. This box is for an outside of the garage. Does it matter if it inside or outside an unatttached garage?
I would think you would need 2 hots, 1 neutral, and 1 ground making the total wires 4. In the artical I understand it to be 2 hots, 1 neutral and 2 grounds. Please explain this to me. | | |  | Uber Member | |
Jun 5, 2008, 09:39 AM
| | | Let's ask a question. What is ground?
1. It is a zero volt reference
2. It's a place where faults go and the fault should not disturb the zero volt reference.
So, let's examine #1. This means that CATV and telephone and the power ground should all be at zero volts.
Now, we add a sub-panel. In order to maintain that 0 volt reference, the ground to the sub must not be bonded to the neutral. So, we have satisfied the requirement that the neutral current from the sub will not disturb the ground reference.
Thunderstrorms/Lightning
A couple of things can happen. During a thunderstorm the Earth's potential can change over a hundred feet or so, hence the necessity to again have a ground at a single point.
Now suppose we get a lightning strike at the unattched structure.
What might happen? That lightning strike will likely dissapate through the ground of the sub back to the main panel. Well, that ground will likely melt. What we would like happen is that the lightning strike be diverted to Earth and it will take the path through the ground rod of the sub panel.
GROUND LOOPS
These are diferences in potential in so called "grounds". These loops are a real pain to eliminate in electronics and you may have to make some compromises along the way. Very little difference in potential can damage electronics. In many cases that ground is common to electrical communication so isolation and differential transmission techniques are used to help elimiinate the problem. (Lots of stuff can go here)
We used to just be concerned with "protective ground". If there was a break down in the insulation of a piece of grounded equipment, the fuse would pop. When power was first generated, we probably only had lamps in the home, so two wires were sufficient. Then there were motors (washing machines) and drills and protective ground came into play. Then came plastics and the idea of "double-insulated" came into play. Now we have GFCI and AFCI's because people don't inspect their electrical wiring and/or don't know what to look for. Incidently, GFCI's don't require a ground to work. 10 mA or so across the heart muscle is enough to stop the heart.
Ethernet is transformer isolated. USB is not. Telephone is an isolated entity. CATV is a grounded entity.
In extremely sensitive buildings, there actually will be two different grounds. One being a clean ground used for communication and another one being a dirty ground used as protective ground. There are also orange colored outlets which have an isolated or independent ground. These are very rare.
I guess a couple of asides:
1) The guy's main breaker box and service entrance was located on the exterior of the building. This is entirely possible.
2) Conduit is used as protective ground. You cannot rely on its integrity. | | |  | New Member | |
Jun 5, 2008, 10:07 AM
| | | KeepItSimpleStupid
That is the best explanation I have ever had given to me. You should write books. I hope this site references back to this link because it is very clear to understand. Wow
Thanks for spending the extra effort. I really do appreciate the feedback and definition.
Thanks! | | | | Thread Tools | Search this Thread | | | | Add your answer here.
Check out some similar questions!
Connecting 3 wire to a 4 wire service panel [ 5 Answers ]
I am trying to connect from a 3 wire system at the utility pole to a 4 wire service panel inside a new mobile home. I called an electrician for some advice and was told that I needed to drive an 8ft ground stake and attach a solid copper wire from the stake to the ground bar in the panel. Then I...
Wire to a 100A sub-panel [ 1 Answers ]
I want to run copper wire from my 200Amp main electrical panel to a 100Amp sub-panel. The 100Amp panel will feed a heat pump compressor, air handler with heat strips (total load = 70 amps) and about 4 20 amp outlet lines. I have previously wired a 60 Amp sub-panel in this house.
The panels would...
Sub-Panel Ground, Wire or Rod [ 9 Answers ]
I running a 70 amp sub-panel to a shop that does have telephone connections to the main house. I know that I need to isolate the ground from the neutral at the sub-panel. I am planning on running 3, #4 wires to the sub-panel and I also have an 8' ground rod, which I will connect as well.
My...
Sub panel wire [ 2 Answers ]
I'm currently building a new home with 200amp service. I have requested the builder to supply 100 amp service to the rear of the home for my detached workshop. My question is a alumaflex type se cable 600 volt awg2-1 cdr awg4 the right cable? I have been told this is only rated at 65 amps? Thanks
Wire needed for a 100 amp sub panel? [ 3 Answers ]
I am installing a 125 Amp Sub panel in a detached shed approximately 100' from the house. The subpanel has a 100 amp main breaker in it and I have a 100 amp breaker that will go in the main house panel to feed it. I will be using #4 copper THHN for my 2 hot conductors and neutral conductor and a #6...
View more Electrical & Lighting questions Search |
|