Ask Experts Questions for FREE Help !
Ask
    redsonlee's Avatar
    redsonlee Posts: 5, Reputation: 1
    New Member
     
    #1

    Jan 19, 2013, 07:08 PM
    How many belden cables can you put in 1 inch emt conduit with 13 # 14 wires
    The same cables.
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #2

    Jan 19, 2013, 09:23 PM
    Are you sure about the AWG of the conductors? #14 AWG conductors carry an current up to 15 amps. What is the number of this Belden cable

    According to the 2008 edition of the NEC, chapter 9, you can put 11 ea. #14 AWG conductors in a Trade Size 1 emt. Which means one cable will cause a violation of the code.

    This figure varies depending on the type of insulation. So we need to know the "TYPE" of conductors that are in the cable.

    For example, are the conductors THHN or THWN?
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #3

    Jan 20, 2013, 06:12 AM
    If they are typical Belden cables you can put a total of none in with any amount of #14 THHN.
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #4

    Jan 20, 2013, 08:41 AM
    Stan,

    The only Belden cables I ever installed were plenum rated, 22 AWG conductors. There were 24 conductors per cable. They were for an IBM dictating system. I never used conduit for them.

    I thought the Belden cable the poster was referencing has 13, #14 AWG conductors inside the sheath. Your interpretation has the #14 AWG conductors in the conduit already.

    I used the THHN / THWN types as part of my example it did not come from the OP. The OP did nor give the type of any conductors.
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #5

    Jan 20, 2013, 09:17 AM
    Stan,

    I did a search at Belden.com and found cable P/N 27091A. This cable has 13 conductors, all #14 AWG. According to the Belden "Conduit Fill Calculator". "One (1) cable will take 53% of trade size 1 EMT conduit.

    No information is given about adjustment, corrections or type.

    The calculator has these disclaimers:

    The runs must be less than 100 ft.
    No bends
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #6

    Jan 20, 2013, 12:35 PM
    Hey guys I just figured out Belden's error.

    They are treating the cable with thirteen #14 AWG conductors as one conductor and taking 53% fill instead of using the "Over Two Conductors" and a conductor fill of 40%
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #7

    Jan 21, 2013, 05:54 AM
    "Belden" cables imply low votlage, which cannot, under most situations, be in same raceway as power wiring.

    This is what Stan is referring to.
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #8

    Jan 22, 2013, 07:03 AM
    TK,

    That's why I asked the OP if he was sure of the AWG of the wires inside the cable. I also checked Belden's site and found a cable with thirteen #14 AWG conductors. To me this suggests a higher than normal size conductor for low voltage.

    I'll dig some more, only because I'm curious now if there is a voltage limitation on this cable that would make it a low voltage cable.
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #9

    Jan 22, 2013, 07:29 AM
    OK -The Belden cable, "P/N 27091A" is an industrial "Tray Cable". Listed as 600 Volts or less.

    It is not to be used in a residential environment. So now I'm curious whether that's the cable the OP has, although we'll probably never know.
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #10

    Jan 22, 2013, 11:49 AM
    redsonlee, are you still alive?
    redsonlee's Avatar
    redsonlee Posts: 5, Reputation: 1
    New Member
     
    #11

    Jan 22, 2013, 10:32 PM
    Sorry I wasn't clear on my question about the belden cable. What I should have said is 6 belden cables 2 wire # 22 gauge and 12 # 14 thhn wires plus one # 16 ground in one inch emt conduit. Is this possible?

    6 belden cables
    12 #14 wires
    1 # 16 ground

    HOPE THIS IS CLEARER
    REDSONLEE
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #12

    Jan 23, 2013, 03:27 AM
    What is the purpose of the Belden cables? And what is the thhn for?
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #13

    Jan 23, 2013, 05:01 AM
    If the #14's are being used for line voltage (120/240/277/480) then it is no good.
    Also, the #16 ground is no good for line voltage, it would need to be #14. I'll say that the EMT would be your actual ground, but in that case the #16 is superfluous.
    redsonlee's Avatar
    redsonlee Posts: 5, Reputation: 1
    New Member
     
    #14

    Jan 23, 2013, 11:29 AM
    # 14 wire is for control power 120 volt
    Belden is for low voltage signal wire for level controllers and valves
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #15

    Jan 23, 2013, 02:45 PM
    Then you cannot mix them in the same conduit.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Minimum distance between emt conduit for data and emt conduit for power [ 1 Answers ]

Minimum distance between emt conduit for data and emt conduit for power?

Can I put 4 12-2 romex in 1 2 inch plastic conduit [ 1 Answers ]

Hi, I am running new branch lines to another part of the house. They will pass vertically through a hallway, then on to new area (in walls) Can I protect four 12-2 branch lines in 1 large pvc conduit. Thanks

EMT conduit [ 7 Answers ]

Hi again guys! I'm running about 8 feet of metal EMT conduit from a baseboard heater, into a junction box in the joist cavities of my basement (ceiling, or first floor joist cavity). The baseboard is 2000 watt, 240 volt, and my code here stipulates that 14/2 will suffice with 15 amp breaker. I'm...

Connect flexible conduit to EMT? [ 2 Answers ]

Can you connect flexible conduit to rigid metal conduit? I am moving a dryer in my basement and I read that you shouldn't straighten an already bent piece of conduit if moving an appliance. I need to move my dryer about 10 feet and would like to use a short piece of flexible conduit to attach to...

Running -- supporting (?) EMT conduit [ 1 Answers ]

Well, again I have a question that the NEC code book seems pretty vague on. I’m looking at Article 348 and 370 – on running conduit. What I’m doing is wiring my “pole barn” (see prev. posts & great ansrs/help on the “branch ckt” and the grounding”). The barn has what they call “girts” …...


View more questions Search