Question
 | |  | | | | 
Feb 11, 2008, 02:03 PM
| | New Member | | Join Date: Feb 2008
Posts: 6
| | | How many 20 watt lights on a 20 amp circuit? I have a 20 amp 120 volt circuit. I have been told that load for a breaker should be 85% of rated capacity and that the formula for determination of required amperage is A=W/V. If this is correct it appears the 14 20 watt undercabinet lights I need would total 2.33 amps. Is this correct? If not, how is the problem worked out? Thanks. | | | | | | |
Answers
 | |  | | |
Feb 14, 2008, 04:22 PM
|
#11
| | Ultra Member
Join Date: May 2007 Location: Florida Keys
Posts: 4,162
| Washington, If you went to work and left the lights on(2300 Watts) or other cuircuit on, Would it be closer to 3 or 8 hours?. |
| | | | | | |  | |  | | |
Feb 14, 2008, 07:12 PM
|
#12
| | Full Member
Join Date: Feb 2008 Location: Pennsylvania
Posts: 248
| Quote: |
Originally Posted by Washington1 Where in the NEC does it say you must consider a residential general lighting load continuous? | It's not NEC, it is just a fact of the way circuit breakers are made. They will trip out after a certain time interval when there is more than 80% rated current draw. Quote: |
Originally Posted by stanfortyman WOW! This is SO wrong it's not funny! | Are you saying that manufacturing breakers that way is wrong or that I am way off base with my explaination? If you don't like being limited to 80% continuous then use a plug fuse panel with type W fuses, but I don't think they are manufactured any more. All plug fuses that I can find now are time delay, I don't know if they will blow after continuous use at less than full load. Can someone enlighten me on that? I have never installed a fuse panel. |
| | | | | | |  | |  | | |
Feb 14, 2008, 07:20 PM
|
#13
| | Full Member
Join Date: Feb 2008 Location: Pennsylvania
Posts: 248
| Quote: |
Originally Posted by shortround3 ...that the formula for determination of required amperage is A=W/V. If this is correct it appears the 14 20 watt undercabinet lights I need would total 2.33 amps. Is this correct? If not, how is the problem worked out? Thanks. | That is the correct formula and you did the math right. However if these are 20w fluorescent tubes you will have to add the ballast losses into the equation to get the total current draw. |
| | | | | | |  | |  | | |
Feb 14, 2008, 07:59 PM
|
#14
| | | Electrical & Lighting Expert
Join Date: Jun 2007
Posts: 741
| Quote: |
Originally Posted by Stratmando Washington, If you went to work and left the lights on(2300 Watts) or other cuircuit on, Would it be closer to 3 or 8 hours?. | Strat,
come on, are you serious!?
To say a residential "General Lighting Load" falls under the 80% rule would be a mis-understanding of code. It's more a design issue, not a code issue. If you want to apply the 80 percent rule to your design, then that's fine.
EP,
Circuit breakers are designed to carry 100% of their rated current while the NEC dictates an 80% application. |
| | | | | | |  | |  | | |
Feb 15, 2008, 01:55 PM
|
#15
| | | Electrical & Lighting Expert
Join Date: Feb 2008
Posts: 1,381
| Quote: |
Originally Posted by EPMiller Are you saying that manufacturing breakers that way is wrong or that I am way off base with my explaination? If you don't like being limited to 80% continuous then use a plug fuse panel with type W fuses, but I don't think they are manufactured any more. | You sir are way off base. This has nothing to do with what I like or dislike.
The 80% rule has NOTHING to do with fuses or breakers.
The NEC dictates the 80% rule under certain circumstances. This applies to fuses or breakers.
A breaker can hold 100% of it's rating FOREVER. This is one reason for the NEC restriction.
You really can't be serious when you say a breaker will trip at 80% of it's rating.
If you like I can drum up some NEC text for you to read up on. |
| | | | | | |  | |  | | |
Feb 15, 2008, 03:11 PM
|
#16
| | Full Member
Join Date: Feb 2008 Location: Pennsylvania
Posts: 248
| Quote: |
Originally Posted by stanfortyman A breaker can hold 100% of it's rating FOREVER. This is one reason for the NEC restriction. | stanfortyman,
I stand corrected. I got the 80% information from an electrician that I got some of my training from and took it as gospel. I went to SquareD and did some research on trip curves. See document 0730CT9801.pdf on their QO line. I also found elsewhere that breakers must be able to open or close at 80% or less of their rating, which would explain why I have found breakers that will not stay ON even though they were working below (but close to) their rating. Once they cooled and the load was changed things were fine.
So we can theoretically run 120 20w incandescent lamps on a 20 amp circuit. Of course the inrush would be around 100 amps, hope you have a GOOD switch. And with manufacturing tolerances what they are, I still would use the 80% rule for design. Don't use these numbers for fluorescent lights or any ballasted light (think CFLs) for that matter. |
| | | | | | |  | |  | | |
Feb 15, 2008, 08:38 PM
|
#17
| | Full Member
Join Date: Oct 2007
Posts: 239
| I agree,,,,,,,,I have been doing this a long time and have yet to see a breaker trip at ONLY 80% for ANY length of time. Although it may be a safe thing to have happen, I would suspect a bad breaker if this actually did happen. |
| | | | | | |  | |  | | |
Feb 16, 2008, 09:36 AM
|
#18
| | | Electrical & Lighting Expert
Join Date: Jun 2007
Posts: 741
| You are welcome for the information! |
| | | | | | | | Thread Tools | | | | Display Modes | Linear Mode | |