    How do you tell the difference between 220 and 110
    I'm installing a new electric range in our kitchen and I pulled out the old separate cook-top and oven and was surprised to see only two wires and a ground coming out of the wall for each appliance. My new range is 220, could I just tie all 4 of the old wires together and change out the 30amp bridged breaker and 50amp bridged to one 220? Any help would be great.
    abcsalem's Avatar
    abcsalem Posts: 70, Reputation: 2
    Junior Member
     
    #2

    Feb 13, 2008, 10:49 AM
    Have you checked your main to see if the feed is dual pole breakers for each circuit?
    How about the way the wires are connected to the breakers, what color wires?
    What is the conditions of the exisitng wires? This might be a good time
    To replace them, as well as update to the latest NEC codes.
    What is the load requirement of your new oven?

    In our house, the existing electrical wiring for our Hotpoint 220v oven/range,
    Is a outlet with 3 wire AL, but the ground isn't connected. This is on a dual pole
    50A breaker. In fact our central-air wiring is done this way, with the ground
    Cutoff at the entrance to the main and not connected. I guess in some years ago,
    Electrician that wired our house, did not believe in grounding 220v.
    Stratmando's Avatar
    Stratmando Posts: 11,188, Reputation: 508
    Uber Member
     
    #3

    Feb 13, 2008, 04:52 PM
    You could cap off the 30 Amp, Can't parallel, then use the 50 for new range, Match receptacle to Plug.
    New Construction and remodel should have 4 wire Cord and receptacle. The wire can be # 6 if Copper.

    abcsalem, you should connect or have ground connected at both ends, This way if a Hot wire touches case, it will trip breaker, Not Become Live, Silently, Deadly.
    Washington1's Avatar
    Washington1 Posts: 798, Reputation: 36
    Senior Member
     
    #4

    Feb 13, 2008, 07:28 PM
    I'm installing a new electric range in our kitchen and I pulled out the old separate cook-top and oven and was surprised to see only two wires and a ground coming out of the wall for each appliance. My new range is 220, could I just tie all 4 of the old wires together and change out the 30amp bridged breaker and 50amp bridged to one 220? Any help would be great.
    From what I'm reading I would say no go! Yet, check to see what size wire you currently have. If it's not a #6 copper or larger, or #4 Alum or larger, then you are out of luck, and would have to run a new branch circuit conductor (#6cu as mentioned above. )

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

220 to 110 [ 7 Answers ]

I'm wanting to run a 110 outlet off my 220 serface unit how do I go about doing this?:confused:

Difference between 110 V and 220 volt rating cable [ 9 Answers ]

In usa domestic voltage is 110 volt whereas in britain and asia we use 220 volt. I was asked that whether can we use american cable for 220 volts supply. I know the current carrying capacity is based on the cross sectional area of the conductor and insulation thickness. In usa AWG is used whereas...

110 to 220 [ 5 Answers ]

We need an outlet that needs to support 220v 27.4 amps. Ihave 2 120 lines at that location both with 20 amp breakers. Could I just use those lines connet them to the new outlet 2 hots and 1 ground. Then get a double poled breaker in place of the other 2 breakers. If so on the new dbl breaker...

Is it 110 or 220? [ 2 Answers ]

Hi, I had 2 outlets installed where there were once a heater and its thermostat. The light on my voltage tester is on for both, but when I plug a clock radio (110) into either new outlet, nothing happens. Is it possible that these new outlets are wired at 220 to accommodate the heater that was...

Getting 110 from 220 [ 3 Answers ]

I have a 3-wire 220V going to my well house. I am wanting to come off the 220 to a 110 outlet. I realize this is not the safest thing to do but it is only temporary. My question is, I know I use one wire so I cut let's say the white wire and connect it to one side of this GFI outlet, Do I connect...


View more questions Search