    mtndiy's Avatar
    mtndiy Posts: 2, Reputation: 1
    New Member
     
    #1

    Aug 18, 2008, 02:07 PM
    Ground rod instead of ground wire?
    I'd like to install an RV outlet (120v, 30amp) in our parking area. Unfortunately, I only have two wires available to that location and adding a third wire would be quite difficult. Can I use the two available wires for hot and neutral and drive in a grounding rod next to the outlet for the ground? The two wires I have available are 6 gauge, already black and white and terminate next to the breaker panel, so can easily be connected to a new breaker. I just don't have a third wire for the needed ground. Thanks!
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #2

    Aug 18, 2008, 02:29 PM
    ABSOLUTELY NOT.
    A ground rod does NOT provide or "create" a ground as we know it for circuit protection and shock safety.
    A fault to a lone ground rod will only serve to electrify the ground around it and bring up worms.
    Washington1's Avatar
    Washington1 Posts: 798, Reputation: 36
    Senior Member
     
    #3

    Aug 18, 2008, 04:06 PM
    I agree with Stan [like always :D].


    Mtn,

    It would be best (and required) to install a new cable with grounding conductor.
    mtndiy's Avatar
    mtndiy Posts: 2, Reputation: 1
    New Member
     
    #4

    Aug 18, 2008, 05:03 PM
    Thanks for the fast replies! A quick follow-on question:

    It was my understanding that if you have a separate building with no metallic connection between it and the main building and you want to set up a sub-panel in the outbuilding, but only have hot and neutral wires running to it, then you can use the neutral wire as a "grounding (neutral) conductor". If I understand correctly, the grounding rod at the outbuilding would be connected to the ground bar in the sub-panel, the neutral wire connected to the neutral bar, and then the two bars are bonded together. I know that the ideal would be running a separate ground wire to the outbuilding (and maybe that's now required by code for new construction?), but I got the impression that this was allowed.

    Assuming that's possible for an out-building, could one treat the RV outlet box like a separate building and bond the neutral to a grounding rod and use that as ground for the RV outlet?
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #5

    Aug 18, 2008, 05:18 PM
    While what you say is true (although removed from the 2008 NEC), it would not apply to your RV recepetacle.

    You are running a branch circuit. This is NOT a feeder, not is it a "separate structure" as it applies to this section of the code.

    Still, in the case you describe, the safety ground does NOT come from the ground rod. It comes from the neutral to ground bond in the panel.
    KISS's Avatar
    KISS Posts: 12,510, Reputation: 839
    Uber Member
     
    #6

    Aug 18, 2008, 08:59 PM
    Need a second opinion on this; Would a GFCI breaker be allowed provided the standard "No Ground, GFCI protected" warning is placed on the outlet and possibly the entrance to the trailer?
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #7

    Aug 19, 2008, 04:07 AM
    No. That allowance is just for replacements.
    Tev's Avatar
    Tev Posts: 232, Reputation: 20
    Full Member
     
    #8

    Aug 19, 2008, 12:31 PM
    Maybe adding a wire wouldn't be as difficult as you think. Tell us where and how these wires are run and maybe there is an easy way to do it you haven't thought of.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Misuse of ground wire as neutral return wire in old house [ 5 Answers ]

Here a problem where the "obvious" solution scares me, need some advice on how to best proceed. My home (built 1920 with knob and tube type wiring) has been upgraded over the years by prior owners, but in many place still has active current in the old wires, in other places it is spliced into a...

Using the ground or (bare) wire for the neutral wire [ 2 Answers ]

I have a problem with some wiring that I ran for an outside motion light. Although the hot leg and ground wires are fine, the neutral wire is defective ( it may have gotten knicked or something). Of course, now the wiring is covered up behind a wall that I do not want to tear into if it can be...

Ground Rod / ground wire [ 9 Answers ]

Hello, I am installing a 100 amp subpanel in my workshop 125' away from my house. I have two ground rods in the ground by the shop, and was wondering if it was necessary to run 4 wires from the house to the shop (two hots, one neutral, one ground), or could I just run the three wires from the...

Can you use Metal Conduit as ground to convert 2 wire to 3 wire? [ 3 Answers ]

I need to convert an old cinder block house from 2 wire outlets to 3 wire by adding a ground to all outlets. Since the entire house is cinder block, all the circuits from the basement breaker box are in flexible metal conduit and metal outlet boxes... Is it possible to use the metal conduit...

Ground wire [ 1 Answers ]

At what point do you have to use a ground wire in lu of metal conduit, Or do you?


View more questions Search