From what I read, the answer is "no go!"
Sounds to me you need 30amps? If you do, then from what you said:
Quote:
|
I have 2 120 lines at that location both with 20 amp breakers.
|
this could mean that your present wires-- possibly 12AWG-- will not meet code requirements for a 30A circuit.
Also, are the two wires a straight run, or do they serve other loads (devices; equipment; etc.).
What are you installing that needs 220 volts @30A?