    labman's Avatar
    labman Posts: 10,580, Reputation: 551
    Uber Member
     
    #1

    Aug 27, 2007, 11:04 AM
    Generator<->house?
    Two recent extended power outages reminded me I still don't have a connection for my generator. Yeah, I managed the fridge, freezer, coffee maker, etc on some extension cords, but the pump would be nice too, and maybe next time the furnace too. So I got a 6250 watt generator for $371. I would hate to spend more than that to connect it to the house wiring legally.

    Anything new or I missed? Suicide cords are out.

    These are popular, in stock at Lowe's, but $250 plus a bunch of wiring for a handful of circuits?
    Gentran Corporation: Generator Transfer switches for home & business

    While I dithered, these seem to have gone up to $70. Biggest problem is they won't fit my box as is. Once I cut the notches in the plate to make it fit, it would no longer be the device that UL approved.
    http://ecatalog.squared.com/pubs/Ele...1100HO0701.pdf

    Even at $150 bucks, I am not sure any of their models would fit. Last year they did offer to make one that would for $250
    Generator InterLock Kit - Introduction

    Well past the point I should instal and $130.
    Amazon.com: Reliance Controls 60-100 Amp Utility Switch for up to 15,000-Watt Generators #TCA1006D: Home Improvement

    Whoa, quite slick, but $700?
    GenerLink.com - About GenerLink - The easy way to connect a home generator

    Anybody have any good ideas?

    Is it OK to temporarily run a flexible cord through a hole in the wall if the hole is big enough for the end to go through?
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Aug 27, 2007, 02:41 PM
    What do you mean by not UL approved?

    The Gentran or that style is a simple method to connect, and offers a mandatory isolation switching, simple to operate during an outage.

    If a Gentran can't fit as close as the flexible conduit that is furnished with it, you can extend the flex with additional flexible conduit and a large junction box.

    With the interlock, it is probably the easiest method, still need to do the input wring from the genset, need to be careful with load in the home as the entire panel is now live. This definitely, with good supervision, provides the most flexibility with everything having power, just watch not to overload the genset.

    I don't see 60/100 amp breaker much use in your case.

    The only other method is a large double pole double throw manual switch. In 100 amp frame talking easy $500.00, plus 100 amp wiring.

    Would be better if the cord could pass through a sleeve, how about a PVC plumbing fitting with the 4" cleanout plug. See speedball for the details, beats the hell out of me. This way here you can open the cleanout and pass the cord and plug through when needed. Cord really should not pass through structure.

    I really don't know any other methods to do this. I think the interlock is the best for you. I have confidence in your supervision during an outage.
    KISS's Avatar
    KISS Posts: 12,510, Reputation: 839
    Uber Member
     
    #3

    Aug 27, 2007, 03:30 PM
    Quote Originally Posted by labman
    Two recent extended power outages reminded me I still don't have a connection for my generator. Yeah, I managed the fridge, freezer, coffee maker, etc on some extension cords, but the pump would be nice too, and maybe next time the furnace too. So I got a 6250 watt generator for $371. I would hate to spend more than that to connect it to the house wiring legally.

    Anything new or I missed? Suicide cords are out.

    These are popular, in stock at Lowes, but $250 plus a bunch of wiring for a handful of circuits?
    Gentran Corporation: Generator Transfer switches for home & business

    While I dithered, these seem to have gone up to $70. Biggest problem is they won't fit my box as is. Once I cut the notches in the plate to make it fit, it would no longer be the device that UL approved.
    http://ecatalog.squared.com/pubs/Ele...1100HO0701.pdf

    Even at $150 bucks, I am not sure any of their models would fit. Last year they did offer to make one that would for $250
    Generator InterLock Kit - Introduction

    Well past the point I should instal and $130.
    Amazon.com: Reliance Controls 60-100 Amp Utility Switch for up to 15,000-Watt Generators #TCA1006D: Home Improvement

    Whoa, quite slick, but $700?
    GenerLink.com - About GenerLink - The easy way to connect a home generator

    Anybody have any good ideas?

    Is it OK to temporarily run a flexible cord through a hole in the wall if the hole is big enough for the end to go through?
    I think you will find this page useful:

    http://www.gvea.com/memserv/GVEA_generator_booklet.pdf
    labman's Avatar
    labman Posts: 10,580, Reputation: 551
    Uber Member
     
    #4

    Aug 27, 2007, 08:45 PM
    I don't have any problem with cutting a couple of notches in the Square D plate and screwing it to my old GE box. But once I do that, it no longer will be exactly what UL approved, will it?

    The Reliance is a double throw 60-100 amp switch. It would work, but no way am I going to disconnect my 100 amp feed and move it to the 100 amp side of the switch myself.

    If I am going to pay somebody to mess with that, likely what I should do is scrap the old GE box and put a Homeline box in that the plate would fit. One approved for all the breakers I am using and with enough spaces for all the neutrals and grounds each on their separate bar.

    If I do that, maybe I should go with arc fault breakers. Trouble is, my bedrooms are wired up with #14 and all the breakers I see are 20 amp.

    On the cord, I was thinking of some sort of a 4'' pipe through the wall and a cap. Just take the cap off and pull the cord out and plug it in.
    labman's Avatar
    labman Posts: 10,580, Reputation: 551
    Uber Member
     
    #5

    Aug 29, 2007, 12:03 PM
    Well, I have ordered an interlock kit, Generator InterLock Kit - Introduction They have agreed to modify their K-8010 to fit my old 2 handle box and still charge $150. I can fix the Coney Island problem with the old box by opening up a new main lug beach. Since the top of the existing box is 67'' high, and the bottom is only 10'' above the dryer, likely the sub panel will have to go to the left. I plan to use a fairly small supply breaker and move the lighter loaded 15 amp circuits to the new box and leave the watt hogs in the old. I need to free up 6 spaces plus get the circuit count down to the 20 on the box label. I will have to add a back feed breaker, a feed to the sub, and I want to add a surge protector. If I used an arc fault breaker to feed the sub and put all the bedrooms in it, would that meet the arc fault requirements for bed rooms? What would be the best way to run all the wires from one box to the other? Run a large conduit nipple through the stud from box to box? Several smaller ones? How many #14's in a 1'' pipe?

    Since the UL approved 1970 main panel had one terminal strip for both ground and neutral, should I be better off leaving it that way rather than modifying it by adding an insulated neutral?

    Who has the best prices on things like breakers and boxes, Lowe's or electrical supplies? Can I really save much messing with Ebay?
    KISS's Avatar
    KISS Posts: 12,510, Reputation: 839
    Uber Member
     
    #6

    Aug 29, 2007, 12:55 PM
    labman:

    You need the isolated neutral in the sub-panel. In the main panel the ground and neutral are the same.

    But, in highly sensitive environments, there is a neutral bus, a protective ground bus and a ground reference bus. Isolated ground receptacles (the orange ones) would have their grounds pulled to the ground reference bus. Grounds to motors and appliances would go to the protective ground bus and they would all be connected together at the main panel. I believe green with yellow stripe would be reserved for the clean ground, green for ground and white for neutral.

    Nowadays they appear to be requiring the telco and cable connections to demark very close to the main panel so that the grounds will be at the same potential.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #7

    Aug 29, 2007, 03:00 PM
    OK cool, now I know what you mean on the UL listing, and you are correct, modifying it at home would violate the listing. I am glad to hear the vendor will do it, and keep the cost the same.

    On the subfeed breaker, won't you need a two pole breaker? I don't think there is one made, if so, then yes all the bedrooms would be AF protected. What brand is your main panel?

    If you can use a straight nip large enough for the wires from the main panel to the new sub, then fine. You may want to use flexible conduit, makes bends etc, easy.

    35 #14 will fit in 1" EMT,33 in 1" FMC (flexible metal conduit), and 36 in 1" GRC (galvanized rigid conduit). As long as the nipple is 24" or less, derating will not be necessary.

    As long as the main panel has the main breaker in it, the neutral and ground need to remain bonded together.

    Believe it or not,Lowe's may sell some parts as cheap if not cheaper than a distributor. They buy stuff by the train loads, and local distributors can have a hard time trying to be competitive. All I can say is price out the bill of material at both and buy the cheapest at each.

    Did I miss anything?
    labman's Avatar
    labman Posts: 10,580, Reputation: 551
    Uber Member
     
    #8

    Aug 29, 2007, 04:51 PM
    My panel is a GE TM210F. I was thinking of maybe only a 40 amp feed breaker since I think I have one on hand. That sounds small for a bunch of 15 amp circuits, but it is 40% of the main, and I will leave the range, A/C, kitchen, garage, laundry, etc. in the main. I am planning on using adjacent wall cavities, a 2'' long 1'' galvanized nipple should leave room for nuts and bushings. I hope many of the wires will reach their new breaker without a splice.

    If GE makes a 60 amp double pole arc fault breaker, I won't find it at Lowe's. Just did a net search on it, and didn't find much. I did find my local supply house was cheaper on Cat 5 cable than Lowe's.

    This means leaving the main and its feed from the meter alone. A huge factor on whether I can do the work with your support.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #9

    Aug 29, 2007, 05:41 PM
    At the ready, sir.Can't wait to help. I love watching people work, that's how I make my living nowadays.

    I like the 60 amp plan, gives some room. 40 maybe too tight, esp with pump motor, reefer, etc.


    I have made splices 30 yr ago still working fine, the trick is twist the wires and use a good quality wirenut, I love 3M Scotchloks. Maybe that's why I love scotch (aka mother's milk)

    I see at GE they only make 1 & 2 pole 20 amp breakers:

    http://www.geindustrial.com/publibrary/checkout/Brochures|DEA-234A|PDF
    labman's Avatar
    labman Posts: 10,580, Reputation: 551
    Uber Member
     
    #10

    Aug 30, 2007, 04:22 AM
    One upside to the whole project is that the better prepared I am for an extended outage, the less likely I will ever have one.

    I have seen your suggestions of wire nuts before. I like them too. I have located what I hope is the neutral to frame link on my generator. I am thinking of cutting it, stripping the ends, and wire nutting it back together, easily undone before connecting into the house wiring, and redone otherwise. I could do a switch too.
    labman's Avatar
    labman Posts: 10,580, Reputation: 551
    Uber Member
     
    #11

    Aug 31, 2007, 08:34 PM
    Thinking about this some more. I still have the problem of the dryer being under the breaker panel. Now if that met code in 1970 when the house was built, as long as I leave that panel there, it should be OK. I assume if I had decided to pay somebody to put a new one in, that the new one would have to meet current codes, 3' of open space? Now if I put the sub panel in the next wall cavity to the main box, where it would be the easiest, it will still be partly over the dryer. No good place to move the dryer. Any limits on how close to the door I can put the subpanel? The next wall cavity over isn't even a full one because of the door. I guess I could surface mount it.

    Digging around today, the 40 amp breaker I remembered having, didn't turn up. If I have to buy one, may as well buy a bigger one.

    Just how important are the arc fault breakers for bed rooms? Do you think eventually retrofitting will be required?
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #12

    Sep 1, 2007, 04:16 AM
    Electrical panels have always needed 30 inch wide clear access with no obstacles. I figured you knew that so I was not going to harp on that.

    36 inch away from the front also needs to be clear.

    The 30in wide does not need to be centered on the panel, it can begin at either edge of a panel. So a panel can go right up against a corner, for example.Just as long as from that corner 30 inch is clear to the other side.

    You can use flexible metal conduit and a junction box to get the panel farther away if needed.

    Making bedrooms AF protected is only required in existing homes if you were to do a major renovation to the bedrooms, where walls were built or drywall was removed.

    Do a search on the net for surplus breaker vendors, we call them breaker whores. If a breaker is still available from a manufacturer, then the costs are very low. Their purpose in life is to handle obsolete breakers, if you need one of those, get ready to bend over. You will be able to find a GE #THQL2160 fairly cheaper than new at HD.
    labman's Avatar
    labman Posts: 10,580, Reputation: 551
    Uber Member
     
    #13

    Sep 1, 2007, 04:57 AM
    So there is no way I can make that code compliant without either moving the panel or dryer?
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #14

    Sep 1, 2007, 05:00 AM
    Sorry to be the bearer of bad news, but, you got it. You know me, not here to be popular.
    Stratmando's Avatar
    Stratmando Posts: 11,188, Reputation: 508
    Uber Member
     
    #15

    Sep 1, 2007, 05:30 AM
    I have had Excellent results with Ebay, Never hurts to look.
    Instead of pipe through wall, how about a box meant for generators, that allows plugging in, No leaking of exhaust.
    labman's Avatar
    labman Posts: 10,580, Reputation: 551
    Uber Member
     
    #16

    Sep 4, 2007, 09:49 PM
    FedEx delivered my plate over the weekend. It looks like it will work. I haven't snapped the main breaker off just to make sure yet. With the breakers I need running about $8 at Lowe's, I doubt it will pay to mess with the net since I only need 2 if I can find a subpanel that will take my old TQP (half size with cross ways contacts) and THQL breakers. It might add up if I found a site that had the breakers, a subpanel, a TVSS, and sold 10-3 with ground flexible cord by the foot.

    As for the dryer, I don't think I am going to worry about it. I only anticipate 2 circumstances where any AHJ will be looking at my panel. Some dark, rainy night, when I have the generator throbbing out back and the lights on, I could get a knock at the door. As long as I have a UL approved interlock, I doubt that guy will worry about the dryer being under it. The other thing is eventually selling the house. I suspect such violations are common, and I may not be forced to correct it. If I am, I could go out and buy a cheap, used, stack washer and dryer. One strong argument against living or dying with code violation is that you may be forced to correct them when you sell.

    When I count poles in the breaker box, is the 20 max counting the main breaker? Counting it, I have 22 slots. I assume I count both the TVSS and the back feed breaker as 2 poles each.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #17

    Sep 5, 2007, 02:54 PM
    LM, your secret is safe with us, and the half million other members and guests of AMHD.
    labman's Avatar
    labman Posts: 10,580, Reputation: 551
    Uber Member
     
    #18

    Sep 11, 2007, 08:14 AM
    Well I am slowly accumulating all the bits I need for my generator hookup. Adding a sub panel to free up room in the main one for the back feed breaker makes a bigger project of it. I spent all weekend at a festival, but did take a side trip to a regional big box store that is much better than Lowe's and HD. I picked up a GE TPL412C 4 slot 125 amp sub panel, a 60 amp breaker, a ground bar kit, a 25' coil of 10-3 with ground, and panel filler strips. Everything but the wire is GE, so listed to be used together. Yesterday I was looking for some 10-4 cord at HD and not finding any. Sure enough somebody came long and asked what I wanted. When I told him, he pulled a full 250' coil of SOOW off the shelf and cut off the 5' I needed. $11.25 plus the end I paid about $16 for. Beats mounting a $50 inlet box up on the side of the house and maybe fishing a wire up through an exterior wall. I still need the #6 THHN wire to go from the 60 amp breaker to the subpoena. Can I use a smaller ground? The bottom of the panel only has 4 knock outs. Can I run more than one 10-2 NM through the larger ones?
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #19

    Sep 11, 2007, 02:22 PM
    A 60 amp circuit requires a minimum of a #10 equipment grounding conductor.

    I believe the larger connectors will accept more than one cable. As usual, refer to the data sheet to see if the part is rated to handle more than one cable.
    labman's Avatar
    labman Posts: 10,580, Reputation: 551
    Uber Member
     
    #20

    Sep 12, 2007, 08:25 AM
    OK, I think I may have seen strain reliefs with more than one indentation for cables. Oh, I guess I need #4 for the conductors with a 60 amp breaker.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

How do I connect my generator to my house? [ 14 Answers ]

Hi I have a 5K generator that I want to connect to my house through the main circuit box in my house.. A friend of mine says there is somekind of on/off box that you connect to open the power coming in then another circuit of some kind the plugs into the generator.. has anybody heard of this? I...

Connecting a generator to my house [ 2 Answers ]

How Can I connect a generator into my house electrical supply?

Generator Help [ 14 Answers ]

OK, next question. I have bought a 6000 watt generator. It has four 110 outlets and one 220 "twist style" outlet. What I want to do is wire it into my house temporarily during winter power outages. I know already it will not run my entire house. We have two sets of gas logs, so heat is not an...

Portable Generator [ 6 Answers ]

I am interested in purchasing a 5000 to 6200 watt portable generator to use during power outages. What are the safety concerns such as rain, snow, how far from any structues must it be used, and can it be placed on a deck? Also would like to here any recommendations as to what model and...

Generator for the house, Guardian? [ 3 Answers ]

Hello all, I asked this question a long time ago, but it seems that I'm finally going to give in and buy one. I thought I could get away with just a portable generator, but after Wilma blew through South Florida, my house will not have power back until November 15th. Luckily, the weather is...