Home > Home & Garden > Electrical & Lighting   »   new pole garage needs wiring

 
Thread Tools Display Modes
Question
 
 
#1  
Old May 3, 2007, 08:34 PM
freberd
New Member
freberd is offline
 
Join Date: Mar 2007
Posts: 11
freberd See this member's comment history on his/her Profile page.
new pole garage needs wiring

We have just had a new garage (30x36)built and we would like to run the electrical wire ourselves. We plan on having a bathroom and all the other normal garage stuff, heater hanging from the ceiling, compressor, security cameras and a washer and dryer in bathroom.

We have a couple questions though if you have the answers that would be helpful.

Do the electrical outlets have to be a certain height off the ground?

What is the suggested wire size for florescent lights?

wire size For wall outlets?

Recommend breaker panel?

Thanks

Reply With Quote
 
     

Answers
 
 
Old May 4, 2007, 01:51 AM   #2  
Electrical & Lighting Expert
tkrussell is offline
 
Join Date: Jan 2005
Posts: 4,563
tkrussell See this member's comment history on his/her Profile page.tkrussell See this member's comment history on his/her Profile page.tkrussell See this member's comment history on his/her Profile page.tkrussell See this member's comment history on his/her Profile page.
There is no height code or restriction for outlets, except for ADA (American Disabilities Act) applications. Best to have the outlets at a convenient height, anywhere from 36" to 48", or where ever you desire.

Use all #12 wire for both lights and outlet circuits. The compressor and dryer may need larger wire sized for the load, typically #10 for the dryer, and could be #12 or #10 for the compressor. Check the nameplate for the amp load of the motor.

Not sure what your question is about the panel. Is one recommended? I would think so with several branch circuits to be served. The panel would need a 4 wire feeder, and at least one ground rod grounding the equipment ground bar in the panel, and keep the neutral and grounds separate.

All general purpose outlets will need to be GFI protected, except those for specific stationary appliances, such as the washer, refrigerator, etc.
  Reply With Quote
 
     


Thread Tools
Display Modes

 
Similar Sponsors

Similar Threads
Question Asker Forum Answers Last Post
Wiring Hot Tub and using a 50 Amp Double Pole GFCI Circiut Breaker RIGHTWAY MAN Electrical & Lighting 8 Oct 10, 2007 08:24 PM
one pole of untied double-pole circuit breaker breaks kurthall Electrical & Lighting 5 Jun 13, 2007 06:16 PM
Trying to change a single pole light switch to a single pole swith with a light below lteuscher Electrical & Lighting 5 Jan 30, 2007 01:01 PM
Wiring single pole thermostat in double pole fixture vjk23 Electrical & Lighting 2 Jan 14, 2007 08:00 AM
wiring my garage for a 230 VAC single phase welder jon mitchell Electrical & Lighting 3 Jan 6, 2007 03:58 AM