    Electric Baseboard Timer
    I Wish To Install A Mechanical Timer In An Existing Electric Baseboard Heating System. What Would I Use And How Can This Be Accomplished?
    The timer should be an hour or less. NOTE: I have a good working knowledge of electricity. I simply need to know about the needed parts.
    Morrowrj's Avatar
    Morrowrj Posts: 345, Reputation: 22
    Full Member
     
    #2

    Dec 7, 2006, 03:45 PM
    Well, it may not be the very best way, but have you considered energy saving timers for electric hot water systems ? I say this because you must ensure what ever timer you use can handle the higher current load of a heater
    rabeau99's Avatar
    rabeau99 Posts: 3, Reputation: 1
    New Member
     
    #3

    Dec 8, 2006, 08:25 PM
    I've had problems getting back to this site . This is my second attempt.Here goes.
    I have a lightly used basement with 2 sections of baseboard heating. i.e. Single thermostat, 240V, double ganged circuit breakers. I want to control the heaters with a manual mechanical timer so the kids don't leave the system on when they leave. I'm thinking an hour or less.
    What parts can I use. To achieve this end? I have a good working knowledge of electric circuits. I need help to come up with an acceptable method.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #4

    Dec 9, 2006, 03:58 AM
    What I think you want is a twist timer, like the one in the photo. However, the timer switch needs to be rated for 15 or 20 amps at 240 volt.

    Unfortunately,I am not familiar with such a timer that can handle 240 volts.

    What can be done is to use a single pole timer , such as the one I offer, and have it control the coil of a 2 pole definite purpose contactor that can handle the heat circuit.

    You can find both the contactor and timer at Grainger.

    The timer can be placed at or near the light switches for the basement, and the contactor can be placed in an enclosure at the panel, and wired to iintercept the heater branch circuit wiring from the 2 pole breaker before it goes out to the heater.

    If this sounds like something you want to tackle and need more help with let me know.
    rabeau99's Avatar
    rabeau99 Posts: 3, Reputation: 1
    New Member
     
    #5

    Dec 9, 2006, 11:56 AM
    Thank You TK. The principle is what I was looking for.You answered the question. I will work with this. That contactor needs 24v for the coil so it looks like I will need a 24v transformer as well. That works.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #6

    Dec 9, 2006, 02:39 PM
    I did not look at the coil voltage just grabbed a picture of a DP contactor. You can do this with 120 volts , you can find a contactor with a 120 volts very easily. I am not sure if the timer will work without 120 volts.
    Morrowrj's Avatar
    Morrowrj Posts: 345, Reputation: 22
    Full Member
     
    #7

    Dec 9, 2006, 03:00 PM
    Just as a follow up there are defenitely 240 volt 15-20 amp timers available. Grainger offers a few 120 volt input timer that are rated to control 240/40-50 amps max.

    http://www.grainger.com/Grainger/wwg...GON&action=Go!
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #8

    Dec 10, 2006, 05:35 AM
    Learn something new everyday.The 240 volt 2000 watt timer wall switch will do the job also. I searched everyone except Paragon.

    Good info, Morrow.
    alimanji's Avatar
    alimanji Posts: 2, Reputation: 1
    New Member
     
    #9

    Mar 15, 2013, 12:14 PM
    I have a problem similar to Rebeau's. We have a Great Room that has warm air heating that is supplemented with baseboard heting that we use when it gets very cold up north here. There are three or four baseboard heters (14 to 16' length)controlled by a single thermostat. I want to control the heaters with a manual mechanical timer so so it switches off after the set time (30 min to say 3 hours) has elapsed. I need to have a decent looking switch as this is upsatirs living space. I am not an electrician but can wire a switch. Any help?

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Baseboard electric heater buzz/hum [ 4 Answers ]

Yesterday I installed 3 Marley electric baseboard resistance heaters in my finished basement: a 2500 watt, 1000 watt and a 750 watt unit. All are 240V running off one 30 amp double pole circuit breaker with 10 gage copper wire. Each heater has it own thermostat. The 1000 and 750 watt units have...

Electric baseboard heaters [ 3 Answers ]

One of my electric baseboard heaters makes a high pitched hum when turned on to 70 degrees, unlike the others. What could be causing this and how can I fix it?

Electric Baseboard Heat ?'s [ 7 Answers ]

Hi All, I have electric baseboard heat in our home, and each room is controlled separately. And this may sound dumb... do I need to have the heat set at a certain minimum temperature for the winter? (we live in MN) Also, is it more cost efficient for me keep them in each room on at a...

Electric baseboard help [ 1 Answers ]

We have just tried to turn on our electric baseboard heat for the season and only one room comes on. There is a thermostat in every room and I can hear them click but no heat is generating. What can be wrong?? We have checked the breakers and they are on and have juice. Please someone HELP me! I...

Baseboard electric heat [ 1 Answers ]

Does anyone have any recommendations for brands/style of baseboard heaters? Have looked at hydrosil, they claim to be efficient but are higher priced units. Are the fluid/gel filled units that much more efficient than the cheaper units? Thanks


View more questions Search