    jeffreyscord's Avatar
    jeffreyscord Posts: 3, Reputation: 1
    New Member
     
    #1

    Jul 7, 2006, 01:38 PM
    Do I need conduit?
    I have a panel in my garage for my garage based workshop.
    I want to run a 220 volt circuit (have have the capacity in the panel to do so).
    My question is whether I need to run the wire inside conduit or can I run romex without conduit.
    The wire will be behind drywall the entire way so it will not be exposed at all.
    If I need conduit does it have to run all the way from my panel to the outlet box?
    Thanks,
    Jeff
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Jul 7, 2006, 01:51 PM
    Romex cable is fine, as long as it is not exposed where it can be damaged. Be sure to be careful where it runs through bored holes in the framing. If the cable through holes in wood framing is closer than an 1-1/4" to the edge, use the metal protector nail plates made for protecting cables and plumbing pipes, to prevent any nalis or screws from piercing the cable.
    jeffreyscord's Avatar
    jeffreyscord Posts: 3, Reputation: 1
    New Member
     
    #3

    Jul 7, 2006, 02:38 PM
    Does it matter if the romex is "free" (not attached to the studs) behind the drywall?
    The drywall is already in place and I don't plan on attaching the romex in any way (just running it loose).
    Thanks again.
    Jeff
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #4

    Jul 7, 2006, 04:08 PM
    If you are snaking behind a finished wall, you do not need to worry about supporting at all.

    Anywhere exposed , it must be supported every 4.5 feet, usually with the correct size cable staples.
    jeffreyscord's Avatar
    jeffreyscord Posts: 3, Reputation: 1
    New Member
     
    #5

    Jul 7, 2006, 06:20 PM
    It will be snaked entirely behind finished wall.
    Thanks for the help.
    Jeff

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Conduit requirements for basement wiring [ 1 Answers ]

I am finishing a basement with stud wall and dry wall. Is there any need for conduit to carry the wires behind the dry wall? I know for an unfinished basement wiring below grade must be in conduit but must it if the walls are finished? Thanks Dschaar

Flexible conduit limitations [ 5 Answers ]

I am rerouting wires in a condo. The original construction has every wire running through rigid conduit. It would be much easier for me to use flexible conduit for the reroutes. Are there any limitations to the length of a flex run? Can sections of rigid conduit be interspersed when it is...

Conduit sizing? [ 4 Answers ]

Hi all! I am relocating my breaker box approx 30 feet from its original location. Installing splice box in the old location for connections. My question is : I have 14 12-2 and 3 12-3 to pull from new box to splice box what size conduit do I need so not to worry about heat build up or de-rating...

Electrical conduit [ 1 Answers ]

I am running a new exterior line to a carport to install two fluorescent lights in the ceiling of a "V" shaped aluminum 2 car carport. The underside of the carport reaches very hot temperatures during the summer months, metal parts are burning hot to the touch. I undersatnd I need to use exterior...


View more questions Search