    Difference between two and three wire 220 well pump
    Is it safe to use a two wire 220 volt water well pump (having three wires) at my home ? I thought all 220 used four wires ! Thank you, Dal.
    KISS's Avatar
    KISS Posts: 12,510, Reputation: 839
    Uber Member
     
    #2

    Dec 31, 2009, 09:23 AM

    Hi Dal:

    The electrical trade is confusing. For your situation: 14/2 is really 3 wires (2 hots and a ground), 14/3 is 4 wires; (2 hots, a neutral and a ground). Neutrals would allow 120 V lamps, pipe heaters etc.

    ALWAYS run a ground. 14/2 with ground MAY be acceptable based on the HP of pump and distance. What we need to know is FLA (Full Load Amps) and distance to size the wire.

    Electric ovens and dryers are very odd because of code enhancements.
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #3

    Dec 31, 2009, 10:31 AM
    There are specific code regulations for wiring pump motors.

    Basically, you need the electrical specifications from the metal tag on the pump.

    I know you said you need 220, but the standard is currently 240 VAC.

    240 is derived from the combinations of two hots.

    For the pump, you need to know whether the pump requires only 240 VAC or 120/240.

    If it is a straight 240, then you only need a two wire with ground. Neutral (White) would be used a hot conductor. With either Black or Red (Sharpie pen coloring) to signify that the White conductor is now a hot conductor.

    Before you run out and purchase conductors, you need to know the amperage required by the pump and the distance from the source to the pump.

    This information is necessary to size the conductors to carry the required voltage and amperage the distance to the pump.
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #4

    Dec 31, 2009, 11:06 AM

    NO, not all "220" uses four wires. In fact NO 240v uses four wires, which implies the circuit has a neutral. The moment you introduce a neutral into the circuit it becomes a 120/240v circuit.

    A typical residential well pump would never be 120/240v. It would be 240v. There are some high-end 3-phase variable speed constant pressure pumps that use a VFD, but that is another issue entirely.

    A 2-wire pump has a built-in starting capacitor, a 3-wire pump is to be used with an external control box, usually near the pressure switch/tank. They are NOT interchangeable.

    A solution to your situation would be a question for a well guy or qualified plumber. I will say, if you have a 2-wire pump it can be wired directly with 240v through the pressure switch.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Submersable Pump - 220 volt - Capacitor Overheating - Pump Shutting Off [ 16 Answers ]

My 220 volt submersable well pump stopped working. We took the capacitor in to be checked one day and it was fine. The next day we took the relay in and it checked out. The following day I pressed on one of the wires that goes to capacitor and the well came on. The wire was old so I knew it...

How do you tell the difference between 220 and 110 [ 3 Answers ]

I'm installing a new electric range in our kitchen and I pulled out the old separate cook-top and oven and was surprised to see only two wires and a ground coming out of the wall for each appliance. My new range is 220, could I just tie all 4 of the old wires together and change out the 30amp...

Hard wire 3 wire to 4 wire 220 service [ 1 Answers ]

How do I hard wire my 3 wire (red,blk & bare copper wires) 220vac cooktop to the 4 wire (black/white stripe,black/red stripe, blk/blk & bare alum wires) in the house supply j-box ?

Hard wire 3 wire to 4 wire 220 service [ 2 Answers ]

How do I hard wire my 3 wire (red,blk & bare copper wires) 220vac cooktop to the 4 wire (black/white stripe,black/red stripe, blk/blk & bare alum wires) in the house supply j-box ?


View more questions Search