Question
 | |  | | | 
May 8, 2008, 07:41 AM
| | New Member | | Join Date: May 2008
Posts: 16
| | | Is dedicated circuit for garbage disposal mandatory? I have two questions:
1) does a garbage disposal need a separate circuit?
2) if it does not, can it share the same 20 amp circuit with the dishwasher? | | | | | | |
Answers
 | |  | | |
May 8, 2008, 12:47 PM
|
#2
| | Junior Member
Join Date: Feb 2008 Location: Alabama
Posts: 154
| I believe a dedicated is required for both units (D/W and Dis) . But Im not 100% positive on that. Would be nice if it were I think.
Mike |
| | | | | | |  | |  | | |
May 9, 2008, 08:11 AM
|
#3
| | Printers & Electronics Expert
Join Date: Aug 2007 Location: Tidewater, Virginia
Posts: 1,794
| Home or commercial use?
***********************************
No, I disagree.
1) You may not attach a disposal to either of the two mandatoy 20 Amp branch circuits designated for the kitchen counters.
2) You may attach a disposal to a general lighting branch circuit or a individual branch circuits.
15 Amp should be sufficient but 20 amp may help smooth out the motor operation.
I can't find the code cites but I will look for them. |
| | | | | | |  | |  | | |
May 9, 2008, 03:09 PM
|
#4
| | Junior Member
Join Date: Feb 2008 Location: Alabama
Posts: 154
| Quote: | Originally Posted by donf
***********************************
No, I disagree.
1) You may not attach a disposal to either of the two mandatoy 20 Amp branch circuits designated for the kitchen counters.
2) You may attach a disposal to a general lighting branch circuit or a individual branch circuits.
15 Amp should be sufficient but 20 amp may help smooth out the motor operation.
I can't find the code cites but I will look for them. |
Don...He never said he was attaching it to a plug at the counter for power.
I think both should be on separate circuit. Dishwasher and Disposal.
It is highly recommended from what i gather |
| | | | | | |  | |  | | |
May 9, 2008, 04:17 PM
|
#5
| | | Electrical & Lighting Expert
Join Date: Feb 2008
Posts: 833
| It is even more common to have the disp and DW on a shared 20A circuit. |
| | | | | | |  | |  | | |
May 9, 2008, 04:26 PM
|
#6
| | Printers & Electronics Expert
Join Date: Aug 2007 Location: Tidewater, Virginia
Posts: 1,794
| Stan,
Thanks, no kidding, I just found the code section I was looking for.
I agree that the FD and the DW can exist on the same outlet, if they are using cord attachment. The can also co-exist on a shared 20 amp branch circuit, from the CB to junction box and then hardwired to the appliances.
However, according to 210.52(B) (2) also states what can be on either of the mandatory two 20 amp Branch Circuits. |
| | | | | | |  | |  | | |
May 9, 2008, 10:48 PM
|
#7
| | | Electrical & Lighting Expert
Join Date: Jun 2007
Posts: 540
| Read the manufactures instructions. It may be a requirement to have them on dedicated circuits per NEC 110.3.
With todays appliances pulling over 10 apms, I would dedicate the dishwasher and disposal. |
| | | | | | |  | |  | | |
May 10, 2008, 02:08 PM
|
#8
| | New Member
Join Date: May 2008
Posts: 16
| Thanks everyone very much for help. I decided to dedicate a 20-amp circuit to DW and another 15 amp to disposal to be on the safe side. Problem is, I ran out of slots in the panel for other needs. But that will be tomorrow's problem. Thanks a lot. |
| | | | | | |  | |  | | |
May 10, 2008, 04:33 PM
|
#9
| | Ultra Member
Join Date: May 2007 Location: Florida Keys
Posts: 3,676
| They do make a double breaker that fits in 1 space. They can't share a neutral. |