Ask Experts Questions for FREE Help !
Ask
    Glaesemann's Avatar
    Glaesemann Posts: 5, Reputation: 1
    New Member
     
    #1

    Dec 6, 2006, 05:56 PM
    Condo/Apt. new 100 amp service - BX wire size?
    Hi All!

    I currently have an old 40 amp service in my pre-war condo. We are allowed to run BX securely attached for a new service.

    The distance is 250 feet. I am looking to get a 100 amp service. What size BX cable should be used for this? Do they make BX large enough for a 250 foot 100 amp service?

    I am also wondering what wire it should be, copper, aluminum?

    Any help before I speak with the electrician and board is greatly appreciated.

    Thank you!

    Tim
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Dec 8, 2006, 06:07 AM
    You need to consult with your electrician, as this is an odd situation.

    A 100 amp panel will need to assume the maximum load is 80 amps, and a 100 amp feeder at 250 feet needs to deliver no less than 3% voltage drop.

    This will need either #3/0 copper or 250 MCM aluminum wire.
    Glaesemann's Avatar
    Glaesemann Posts: 5, Reputation: 1
    New Member
     
    #3

    Dec 8, 2006, 06:37 AM
    I was just trying to prepare before I spoke with my electrician and my condo board.

    My electrician quoted 2/3 BX.

    $2000 in BX alone!!

    Yikes!

    Job starts today. No choice I guess.

    Thank you.

    Tim
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #4

    Dec 8, 2006, 12:01 PM
    Yes I know that copper is expensive, aluminum for feeders is much less.

    So someone is running 250 feet of #2/3 copper cable for a 100 amp serivce?

    I will be very interested in the voltage drop.

    Mind you, if the electrician measures the voltage when he is done, with no or little load, the voltage reading will probably be OK, the voltage drop will become evident as more load is applied.
    Glaesemann's Avatar
    Glaesemann Posts: 5, Reputation: 1
    New Member
     
    #5

    Dec 8, 2006, 12:09 PM
    He played this fact down. He said it only mattered if you had "voltage sensitive" items on the load.

    I told him I DO have voltage sensitive items on the load. I am an audiophile and would love to see as little voltage drop as possible.

    He assured me it was only an issue with sensitive computer equipment.

    I am glad you mentioned this. I am going to ask some more questions.

    He didn't come today after all this, because they had an emergency job.

    Would conduit and 2/0 be the correct wire method to avoid voltage drop?

    Thank you!

    Tim
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #6

    Dec 8, 2006, 01:55 PM
    If #2 copper is 250 feet long, with a reasonable load of 50 amps, the voltage drop will be 4.9 volts, or 4.8%.

    Maximum recommended voltage drop for a feeder is 3% to the distribution point, or the breaker panel.

    #2/0 will offer 2.5 volt drop (2.1%) for the same load. An 80 amp load will result in a 3.25% Vd.

    This is acceptable if the branch circuit wiring is not too long, as the final Vd at the outlet should not be more than 5%.

    If this was my job I would be selling you #2/0 Aluminum in PVC conduit (if PVC is allowed in your area) The Vd is still a bit high for 80 amps, but here is where what are the chances of a full load being applied. For a 50 amp load the Vd is perfect,2%.

    What does the local electrical inspector say about this?
    Glaesemann's Avatar
    Glaesemann Posts: 5, Reputation: 1
    New Member
     
    #7

    Oct 17, 2009, 01:28 PM
    Resurrecting this thread because we are finally go ahead with the upgrade and right back where we were 3 years ago. :-)

    It looks like we are going with two 2/0 for the 200 foot run. My question is can we still use our 100 amp (2x100 amp) loadcenter?

    Thanks all.

    Tim
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #8

    Oct 18, 2009, 03:28 AM
    Sure can, just will need to handle the large wire size at the terminals, which may not be large enough to take the 2/0. Either change out the lugs, or reduce the wire size with short pieces of #2.
    Glaesemann's Avatar
    Glaesemann Posts: 5, Reputation: 1
    New Member
     
    #9

    Oct 18, 2009, 05:17 PM
    Great!

    This is a two step install. Meaning the electrician is completing an upgrade of the kitchen wiring and also the loadcenter. He will break the feed in the basement (one floor below) and install the 2/0 from the break (junction) to the loadcenter. The 2/0 will splice to the current #8 at the break junction box. Is it okay to have 2/0 from the box going to a junction with #8 that runs for 200 feet to the service?

    My last question, I promise!

    Thank you!

    Tim
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #10

    Oct 19, 2009, 04:09 AM

    You can post as many questions as you like.

    What is the #8 for?
    Tev's Avatar
    Tev Posts: 232, Reputation: 20
    Full Member
     
    #11

    Oct 19, 2009, 05:51 PM

    #8 is not large enough for a 100 amp service. You need the 2/0 running the full distance. It blows my mind that the "electrician" would even consider using #8 for this. It was fine for your old 40 amp service but it's not even close to what is needed for 100 amps. I'd find a new electrician if I were you.
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #12

    Oct 20, 2009, 08:07 AM
    Please check T310.15. For a 100 A. Main Panel Feed, you can use #4/3 AWG cable.

    Any cable smaller than a 4/3 cable would violate the NEC code.

    You will also need to check with the LAHJ for condo installations to find out who is allowed to do work on Condo electrical systems. (correction to NEC reference.) Then I would ask to see the license for the electrician that is scheduled to do this work.

    Given the history you have chronicled here, I'm very suspect of your electrician's qualifications!
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #13

    Oct 20, 2009, 11:39 AM
    Don, the issue is voltage drop due to a 250 foot length. The #4 is a minimum feeder size, and is irrelevant to the topic.

    Also, would you please direct me to the Condo code in the NEC?

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Wire size in a 100 amp breaker [ 1 Answers ]

I was wondering if a 2/0 wire will fit in a siemens 100 breaker? Thanks for your help

What size wire to use for new service? [ 2 Answers ]

We are currently building a greenhouse, and I need to run about 240 foot of wire from the pole to the greenhouse breaker box. The greenhouse will have 2- 115/230V fans drawing 6.0 amps each, 3- 1/3hp sump pumps not sure of the amperage yet but will be 115v, LP gas instant hot water heater, 10...

Wire Size For 200 Amp Service [ 2 Answers ]

Recently purchased new mobile home with a 200 amp breaker inside.the distance between the outside pole and inside breaker is about 70 feet.what size,or type,or gauge wire do i need to run. Lost in paradis... :) :confused:

4 wire home service entrance wire size [ 1 Answers ]

Mobile home requires 4 wire electrical service entrance wire. Distance is 160 foot from meter to breaker panel. 220V service. What size wire do I use? Can I use diff. size for neutral and ground?

How do I figure out what size wire to use on a 200 amp service. [ 2 Answers ]

My question is... how do I figure out what size wire to use when I know the Amperage of the electrical device. Is there some form of electrical calculation? For example I want to upgrade to a 200 amp panel from a 70 amp panel.


View more questions Search