    BAMBAM's Avatar
    BAMBAM Posts: 10, Reputation: 1
    New Member
     
    #1

    Jul 20, 2005, 08:25 AM
    Condenser wiring
    Hi, I am installing wiring for a new central air condenser that is being installed next week, and I wanted to make sure I was not missing anything. The HVAC installer told me that I needed #8 and 40 amps. I have a flexible whip to go from the disconnect to the condenser and have run (2) #8 wires plus a ground across my basement to the breaker box. I bought a 60 A disconnect box (is this the proper size? Only size Lowe's had) and it has an on/off switch rather than a pull out or a fuse style. Does the type matter? Inside this box I assume I hook up the wires from the circuit breaker to the line terminals and the wires from the condenser to the load terminals, is this correct? Finally I wasn’t quite sure which circuit breaker to buy, I know 40 amps and I’m pretty sure it’s a 2 pole, and hacr but other than that is there anything to the circuit breaker selection? Anything else I might need to know to keep this wiring job up to code would be helpful. Thank you.
    TOOL_5150's Avatar
    TOOL_5150 Posts: 10, Reputation: 1
    New Member
     
    #2

    May 26, 2007, 01:49 AM
    Do not use a 60 amp breaker on #8 wire. You need to install a 40 amp breaker at your sourse [subpanel] then take that to a disconnect box. Depending on the area you are in, it can be fused or not. If it does have to be, then the fuses, or breaker needs to be 40 amps. The disconnect box needs to be next to the condenser unit. Hope this helps!
    Stratmando's Avatar
    Stratmando Posts: 11,188, Reputation: 508
    Uber Member
     
    #3

    May 26, 2007, 06:58 AM
    60 Amp Disconnect Enclosure OK. Use 40 amp breaker for protection at panel. Disconnect can be switch, pullout, and could use 60 Amp for Disconnect, Wires are already protected at panel. I would pull a pair of #12's with power to both units for compressor control wires.
    After rereading your post, I notice you say compressor.Usually pair of #10's(30 Amp)for
    Compressor Unit. Air Handler would be the 40 Amp.
    If money not a major problem, I would pull #6's. Still 40 Amp breaker. Less loading down and ready for future upgrade.

Not your question? Ask your question View similar questions

 

Add your answer here.


Check out some similar questions!

Condenser wiring [ 5 Answers ]

Hi, I am installing wiring for a new central air condenser that is being installed next week, and I wanted to make sure I was not missing anything. The HVAC installer told me that I needed #8 and 40 amps. I have a flexible whip to go from the disconnect to the condenser and have run (2) #8 wires...

Condenser Fan Wiring [ 2 Answers ]

I Purchased A New Condenser Fan. The Old Fan Had Three Wires One To The Contactor(black) Then Yellow Wire To The Capacitor And Brown Wire To Capacitor. The New Motor Has Four Wires Brown , Brown With White Strip, Black And Purple. The Fan Diagram Shows You Can Connect With Only Three Wires. It...

Air Cond condenser Fan Motor Wiring [ 2 Answers ]

Does anyone know? I have two black wires on my outside condenser fan that are no different that hooks in to a black wire and a white wire coming out of my new fan motor. Can they be swiched? If not I don't know how to tell which wire to hook the black and white up to. Also it has a brown and a...

Wiring Outside A/C condenser Fan Motor [ 1 Answers ]

Need help wiring a new outside a/c condenser fan motor. Old fan motor has 3 wires: black, blue, light orange. Black to one side of contact, light orange to other side. Blue to capacitor. Contact has 5 connectors.. one side: black from motor, black to inside the condenser. Other side: dark orange...

Wiring AC condenser to Breaker Box [ 2 Answers ]

I have recently purchased a home that had a few vandal problems. It seems someone was trying to steal most of the pieces to the breaker box while it set empty during sale. The closing company had most of it repaired during closing, but turns out today *the hottest day in a month* the wire from...


View more questions Search