Question
 
 
#1  
Old Feb 3, 2008, 02:48 PM
n8xwb
New Member
n8xwb is offline
 
Join Date: Feb 2008
Posts: 1
n8xwb See this member's comment history on his/her Profile page.
Circuit Breaker didn't Trip

I have a 1 year old home. The bathroom outlet is a GFCI outlet on a circuit protected by a 15 amp ARC FAULT BREAKER. Today my wife plugged her hair blowdryer and the base of the cord lit up like an arc welder. This lasted for 5-8 seconds before the cord completely melted and the fireworks stopped. Apparently the cord was frayed and shorted out?! Neither the GFCI or ARC FAULT BREAKER tripped!!! Does this indicate that we have some kind of wiring problem??

Reply With Quote
 
     

Answers
 
 
Old Feb 3, 2008, 04:42 PM   #2  
Engineering & Electronics Expert
KeepItSimpleStupid is offline
 
KeepItSimpleStupid's Avatar
 
Join Date: Aug 2007
Posts: 5,261
KeepItSimpleStupid See this member's comment history on his/her Profile page.KeepItSimpleStupid See this member's comment history on his/her Profile page.KeepItSimpleStupid See this member's comment history on his/her Profile page.KeepItSimpleStupid See this member's comment history on his/her Profile page.
The GFCI should not have tripped. They don't trip on short circuits.

The AFCI, I believe, should have tripped on two conditions:

1) The AFCI condition of sparks
2) The breaker should likely have tripped on overload.
  Reply With Quote
 
     
 
 
Old Feb 4, 2008, 12:02 PM   #3  
Home Repair & Remodeling Expert
ballengerb1 is offline
 
Join Date: Dec 2006
Location: Wheaton, Illinois, USA
Posts: 10,157
ballengerb1 See this member's comment history on his/her Profile page.ballengerb1 See this member's comment history on his/her Profile page.ballengerb1 See this member's comment history on his/her Profile page.ballengerb1 See this member's comment history on his/her Profile page.ballengerb1 See this member's comment history on his/her Profile page.ballengerb1 See this member's comment history on his/her Profile page.ballengerb1 See this member's comment history on his/her Profile page.ballengerb1 See this member's comment history on his/her Profile page.
Maybe I have been doing this wrong but the arc faults are required by code for new construction bedrooms. They can be used in other circuits but are only designed to prevent a fire caused by arcing. Your arc fault should have tripped but did not for some reason so it needs replacing. You can buy a combination GFCI and ARCI breaker and protect the hole line from the panel.
  Reply With Quote
 
     
 
 
Old Feb 4, 2008, 12:15 PM   #4  
Junior Member
Sand Daddy is offline
 
Join Date: Feb 2008
Posts: 95
Sand Daddy See this member's comment history on his/her Profile page.
Send a message via Yahoo to Sand Daddy
A GFCI is a ground fault current interrupter, meaning if there is a short to ground it will pop. The breaker is designed to prevent too much current from being pulled on the line and to stop a hard hit, in this case it was probably on a 15amp breaker.

What happened to you is essentially a bad dryer. Typical new homes use #12 thhn supplied to the outlets. The amps being pulled by the dryer was enough to melt down the smaller gauge cord feeding the dryer but not enough to overload the breaker. The reason it took so long for the sparks is that the insulation on the cord had to melt away exposing the live line wire to the ground. Once this occurs, spark, bang pop!

The GFCI should have tripped at this point. Replace the dryer, double check the electrical.
  Reply With Quote
 
     
 
 
Old Feb 4, 2008, 01:03 PM   #5  
Engineering & Electronics Expert
KeepItSimpleStupid is offline
 
KeepItSimpleStupid's Avatar
 
Join Date: Aug 2007
Posts: 5,261
KeepItSimpleStupid See this member's comment history on his/her Profile page.KeepItSimpleStupid See this member's comment history on his/her Profile page.KeepItSimpleStupid See this member's comment history on his/her Profile page.KeepItSimpleStupid See this member's comment history on his/her Profile page.
Sand Daddy:

A typical hair dryer has no ground. Only a hot and neutral, thus there can be no short to ground. There could, however, be a leakage path through the body, but there is no way of knowing. That path only needs to be a few milliamps.
  Reply With Quote
 
     
 
 
Old Feb 4, 2008, 02:33 PM   #6  
Junior Member
Sand Daddy is offline
 
Join Date: Feb 2008
Posts: 95
Sand Daddy See this member's comment history on his/her Profile page.
Send a message via Yahoo to Sand Daddy
KeepItSimpleStupid, this is true. There is a neutral however which will yield the same results. Short to the Neutral or ground will cause the above scenario.
  Reply With Quote
 
     
 
 
Old Feb 5, 2008, 07:41 AM   #7  
Senior Electrical & Lighting Expert
tkrussell is offline
 
Join Date: Jan 2005
Posts: 4,723
tkrussell See this member's comment history on his/her Profile page.tkrussell See this member's comment history on his/her Profile page.tkrussell See this member's comment history on his/her Profile page.tkrussell See this member's comment history on his/her Profile page.
Does the Test Button on any GFI or Arc Fault breakers trip the breaker?

This test is to be done once a month.

The AFCI breaker should have sensed the arcing occurring between the two wires of the cord.
  Reply With Quote
 
     
 
 
Old Feb 5, 2008, 08:19 AM   #8  
Home Repair & Remodeling Expert
ballengerb1 is offline
 
Join Date: Dec 2006
Location: Wheaton, Illinois, USA
Posts: 10,157
ballengerb1 See this member's comment history on his/her Profile page.ballengerb1 See this member's comment history on his/her Profile page.ballengerb1 See this member's comment history on his/her Profile page.ballengerb1 See this member's comment history on his/her Profile page.ballengerb1 See this member's comment history on his/her Profile page.ballengerb1 See this member's comment history on his/her Profile page.ballengerb1 See this member's comment history on his/her Profile page.ballengerb1 See this member's comment history on his/her Profile page.
That was my read on the situation yesterday, the ARCI should have picked up the arcing in the dryer. The reason you should test your faults each month is obvious, they do break down.
  Reply With Quote
 
     


Thread Tools
Display Modes

 
Similar Sponsors

Similar Threads
Question Asker Forum Answers Last Post
Theory of vacuum Circuit Breaker & sf6 circuit breaker prashantkolhe Engineering 1 Apr 22, 2008 06:55 PM
Replacing Circuit Breaker with Higher AMP Breaker MsHartline Electrical & Lighting 8 Sep 24, 2007 02:18 PM
replacing a circuit breaker with a GFI breaker- q on neutrals jsarson Electrical & Lighting 1 Feb 11, 2007 11:54 AM
Circuit breaker failed to trip chappers Electrical & Lighting 2 Oct 30, 2006 03:17 AM
Breaker doesn't trip mbridges Electrical & Lighting 3 Jun 15, 2005 02:44 PM