| Yes install the 2 pole 100 amp breaker in the main panel. The feeder to the garage panel can be either 3- #2 Al for the two hots and one neutal and 1- #4 for the equipment ground. or you can use 3-# 3 copper for the hots and neutral and 1-# 8 for the ground.
Be sure to isolate the neutral and equipment ground at the sub panel. The neutral is already insulated, just be sure there is no main bonding jumper, which ususally is a screw that is driven thru the neutral bar and threads into the panel backbox. The equipment ground must connect directly to th backbox, along with all the equipmnet grounds from the bracn circuits.
If you have any other questions, please get back here with them. |