Question
 
 
#1  
Old Apr 22, 2007, 08:27 PM
wdixielou
New Member
wdixielou is offline
 
Join Date: Apr 2007
Posts: 1
wdixielou See this member's comment history on his/her Profile page.
Change 220 motor to 110

After I have changed the motor per the diagram on the motor do I have to change the way the cord(plug in) is attached to the motor in any way? Can I just change the plug in to adapt to a 110 outlet?

Reply With Quote
 
     

Answers
 
 
Old Apr 23, 2007, 02:34 PM   #2  
Senior Electrical & Lighting Expert
tkrussell is offline
 
Join Date: Jan 2005
Posts: 4,723
tkrussell See this member's comment history on his/her Profile page.tkrussell See this member's comment history on his/her Profile page.tkrussell See this member's comment history on his/her Profile page.tkrussell See this member's comment history on his/her Profile page.
The 120 volt plug should be different that the 220 volt plug. Each plug is rated for specific voltages. So if the motor needs a 15 amp 120 volt straight blade plug, you need a NEMA 5-15P plug, which is your standard every day plug,and wired accordingly with the hot, neutral, and equipment ground.
  Reply With Quote
 
     
 
 
Old Apr 27, 2007, 07:11 PM   #3  
New Member
darkmas is offline
 
darkmas's Avatar
 
Join Date: Apr 2007
Location: San Francisco, CA
Posts: 2
darkmas See this member's comment history on his/her Profile page.
BTW, be prepared to pay 2X the cost to run the same motor for an equal number of hours. Generally you want to convert single phase 110v motors to 220 when possible, not the other way 'round.

-Bill

Comments on this post
TheSavage agrees: Wrong --the costs is close to the same to run -- the advantage of 220 it you can run smaller wire -- Savage
  Reply With Quote
 
     
 
 
Old Apr 28, 2007, 12:28 AM   #4  
Senior Electrical & Lighting Expert
tkrussell is offline
 
Join Date: Jan 2005
Posts: 4,723
tkrussell See this member's comment history on his/her Profile page.tkrussell See this member's comment history on his/her Profile page.tkrussell See this member's comment history on his/her Profile page.tkrussell See this member's comment history on his/her Profile page.
Dark, could you show how a motor will cost more to run at 110 volts?

Comments on this post
TheSavage agrees: yup -- use ohms law -- Savage
  Reply With Quote
 
     
 
 
Old Apr 28, 2007, 07:06 PM   #5  
New Member
shuntripper is offline
 
Join Date: Apr 2007
Location: Northern CA
Posts: 27
shuntripper See this member's comment history on his/her Profile page.
Hmm, won't let me agree with TK, but I do anyway. A real reason for stepping up to higher voltages is they pull less amperage to do the same work. True, this allows use of smaller wire but one real advantage is that you get more equipment out of a distribution point. Example: a 120/277V panel can have 16 120W lights pulling 1A each on a single 120V/20A CB. A 277/480V panel can have 36 on a 277V 20A CB. More than double the amount of area lit up. Another reason is big motors would be absolutely humungous (Spelling?) if they had to run on the lower voltages.
  Reply With Quote
 
     
 
 
Old Apr 28, 2007, 07:43 PM   #6  
Senior Member
TheSavage is offline
 
Join Date: Oct 2006
Posts: 564
TheSavage See this member's comment history on his/her Profile page.
Quote:
Originally Posted by shuntripper
Hmm, won't let me agree with TK, but I do anyway. A real reason for stepping up to higher voltages is they pull less amperage to do the same work. True, this allows use of smaller wire but one real advantage is that you get more equipment out of a distribution point. Example: a 120/277V panel can have 16 120W lights pulling 1A each on a single 120V/20A CB. A 277/480V panel can have 36 on a 277V 20A CB. More than double the amount of area lit up. Another reason is big motors would be absolutely humungous (Spelling?) if they had to run on the lower voltages.
ok same situation you run 2 lines -120 v- = 16 bulbs each x2 = total 32 bulbs -- you would get the same # of bulb on a 240 20 amp breaker -- ohms law -- when you throw the 277 figure in there you confuse the issue for folks that are learning and that is not used in homes. -- Savage
  Reply With Quote
 
     
 
 
Old Apr 30, 2007, 07:54 PM   #7  
New Member
shuntripper is offline
 
Join Date: Apr 2007
Location: Northern CA
Posts: 27
shuntripper See this member's comment history on his/her Profile page.
But you had to actually apply the formula to see if my figure was correct didn't you? And you'll never get me to call a lamp a bulb. I'm not in the habit of speaking down to people. Ignorant people never ask questions, that's how they remain ignorant. And what is so difficult about the concept that the number 277 is greater than 120? It's a real world example. Give them some credit. Ohm's law still works the same way. How many 240V lamps have you ever seen anyway? ballasts use the greater line voltages, not the lamps.
  Reply With Quote
 
     


Thread Tools
Display Modes

 
Similar Sponsors

Similar Threads
Question Asker Forum Answers Last Post
220 to 110 joey b Electrical & Lighting 7 Apr 6, 2008 11:45 AM
Water heater 110 or 220 lmanwarren Electrical & Lighting 7 Nov 3, 2007 06:13 PM
110 vs. 220 wiring... CharlesMHolloway Electrical & Lighting 7 Sep 17, 2007 11:32 AM
changing motor from 220 to 110 handymanTaylor Electrical & Lighting 3 Dec 17, 2006 04:26 PM
getting 110 from 220 simpson Electrical & Lighting 3 Oct 23, 2006 09:44 AM




Copyright ©2003 - 2007, Ask Me Help Desk.
All times are GMT -8. The time now is 07:29 AM.