    Can a hood be on the same 20A circuit with already 2 duplex GFCI receptacles
    In my kitchen I have 2 duplex GFCI receptacles above the countertop on one 20A circuit.
    I cannot pull an extra wire through the existing conduit so would like to hook up the hood and the range (all gas but needs power for the electronics) on that same circuit.

    Does the NEC 2005 code allow for that or do I need to install a separate circiut? I live in Illinois - USA.

    Thanks
    Jack
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Jan 20, 2008, 01:27 PM
    What you propose s fine, and allowed.
    jackp's Avatar
    jackp Posts: 2, Reputation: 1
    New Member
     
    #3

    Jan 20, 2008, 01:53 PM
    TKrussel, thanks for the quick reply. The additional outlet specifically for the range will be placed hidden behind the range. Does is need to be GFCI?

    About my kitchen island. I have one big countertop (48x96 inches). I read somewhere that I only need 1 duplex receptacle GFCI as this is considered 1 countertop. Is that correct or do I need more?
    Can I place them below the countertop as I have nothing to place them above. With below I mean on the backwall of the island where I have to reach like 6 inches underneath the island countertop (which is sticking out on the back) to reach it. It will be nice out of sight this way and we don't plan on using. It is more to pass inspection later.
    How many inches below the countertop can I place it?

    More questions than I thought. Sorry...
    thanks
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #4

    Jan 22, 2008, 07:06 AM
    No, the outlet for a gas range does not need to be GFI protected.

    As long as the islnad does not have any range, cooktop, or sink, this counter will only need one GFI outet.

    I would recommend at least two, but that is up to you.


    You may locate the outlet anywhere.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

15A receptacles on 12/2 GFCI Circuit [ 5 Answers ]

I was just looking at some of the wiring that was done in my house when it was built in 2003. I have one GFCI Circuit that has 5 receptacles on it. On this, it is wired all with 12/2 to the garage first, where the receptacle is the GFI, then it runs 3 outdoor receptacles, and 1 in the basement. ...

Can receptacles and lights be wired on the same circuit? [ 1 Answers ]

Hi, I a do it yourselfer who wanted to do some wiring in an addition. I was wondering if receptacles and lights can be wired together on the same circuit? Also, is it better to use 14 wire and then less wattage or 12 wire and then more loads? And what about bathrooms do they need to be on...

20amp circuit breaker, 15 amp receptacles [ 2 Answers ]

I have a 20amp circuit breaker with 15 amp receptacles and light switches on #12 wire with a load of 1700, is this allowable? If not, and I change to a 15 amp circuit breaker, is the 1440 watt safety load in the code or is it a non-code safety suggestion?

GFCI Circuit Breaker. [ 2 Answers ]

I recently ran a branch circuit to the exterior of the house to add a receptacle on the patio. The existing 15 amp breaker protected a circuit that had only three plug outlets and one switched ceiling light. The circuit is very lightly used. So I want to add GFIC protection in the form of a breaker...

Wiring a switch and GFCI circuit [ 3 Answers ]

I am in the process of wiring my bathroom. The lighting and fan circuit has one fan, one overhead light and one vanity light. I was wanting to use a NuTone single space / 3 switch unit for all three. Wiring that is all very straight forward but the fan requires a GFCI circuit to make it OK for over...


View more questions Search