    Bathroom GFI outlet trips breaker at breaker panel
    Hello all. Our house is approximately 13 years old. Each morning when both the iron and blow dryer is plugged into two separate GFI outlets in the master bathroom, the circuit will trip the 15 amp breaker in the breaker panel.

    Is it possible to upgrade the breaker to a 20 amp without overloading the existing wire? (It's rare that the blow dryer and iron are on at the same time, but when we don't think about it and plug them both in - trip)

    Am I mistaken to believe that the circuit should be tripping at the GFI outlet instead of the breaker at the panel? Is it possible that my GFI outlet is faulty and could just use replacing even though it tests fine using its own test button?

    Any light you could shed on this is greatly appreciated.
    Stratmando's Avatar
    Stratmando Posts: 11,188, Reputation: 508
    Uber Member
     
    #2

    Oct 7, 2008, 02:30 PM

    The GFI is to trip if there is a difference of current being drawn from the hot and neutral.
    It's probabbly OK
    If you have #12 wire, you can increase to a 20 amp breaker. Is their a circuit on the opposite side of the wall you can get to same bath, could have 2 circuits, then neither would blow.
    Needs to be wired so both can be on at the same time, or use 1 at a time.
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #3

    Oct 7, 2008, 02:33 PM
    A GFI is NOT a circuit breaker, so it will not trip on an overload.

    Your situation is common which is why they changed the code to require 20A circuits in bathrooms.

    Other than running a new circuit to one of the rooms you have to live with the occasional tripping.

Not your question? Ask your question View similar questions

 

Add your answer here.


Check out some similar questions!

Breaker in panel periodically trips for pool outlet [ 1 Answers ]

I have a gfi outlet outside in which I have connected a timer for the above ground pool all seemed to be going well but lately it trips the breaker 15 amps in the main panel what could cause this

New 15A breaker trips main 100A breaker [ 6 Answers ]

Hi, I've been finishing my basement and I added a few 15A breakers One room has 8 outlets in series with the first starting about 6 feet from the main panel. There is currently no load on this outlets. When installing the drywall I accidentally shorted the outlet closest to the panel. It...

Bathroom or outside Breaker panel installation. [ 2 Answers ]

I asked this before, but can not find the answer.. I am installing a 150 amp service, and originally was putting the breaker box etc in a 1/2 bath.. and was told, that is not proper.. So, I can install same unit, opposite wall, but will be outside, under a totally dry balcony type place, and I...

How to wire an 15amp dedicated outlet from breaker panel to kitchen [ 1 Answers ]

I need to put a 15 amp outlet that has its own breaker in my kitchen above the cabinets or in cab over oven. This is for a microwave oven. Thanks in advance for any help!

GFCI on breaker panel trips, 3 way, how to find the problem? [ 1 Answers ]

Periodically one GFCI in the panel trips This particular circuit runs an outside outlet, one light in the basement and it seems to work 2 switches and a plug in the family room The problem with the 2 switches in the family room at opposite ends are suppose to turn the plug off and on as a 3...


View more questions Search