Asked Oct 10, 2009, 11:09 PM — 7 Answers
Hey All, Maybe you can help.

I'm installing four 240V baseboard heaters to a room in the back of my house with a total amp rating of 17.7 amps. I intended to use a double pole 20 amp breaker and 12/2 romex, but my brother says I should use a 30 amp breaker and 10/3 wire. The furthest heater is about 30 ft from the main panel. Is the additional sizing necessary or just a nice thing to do?

7 Answers
KUXJ's Avatar
KUXJ Posts: 975, Reputation: 484
Senior Member
 
#2

Oct 11, 2009, 12:51 AM
Hi! Chrisbosco, and welcome to AMHD

Quote:
Originally Posted by chrisbosco View Post
Hey All, Maybe you can help.

I'm installing four 240V baseboard heaters to a room in the back of my house with a total amp rating of 17.7 amps. I intended to use a double pole 20 amp breaker and 12/2 romex, but my brother says I should use a 30 amp breaker and 10/3 wire. The furthest heater is about 30 ft from the main panel. Is the additional sizing necessary or just a nice thing to do?
Quote:
Is the additional sizing necessary or just a nice thing to do
When It comes to electricity, I would rather be right, than dead.

My idea of being "nice" would be sleeping inside while the heaters were humming along, instead of outside watching the fire co. Do it's job.

I'm a DIY'er myself, and I've learned there a reasons why codes are written.

Let's consider:
Code states you have to have 125% of load.....
Your 17.7amps = 22.125

So your plan of 1 D.P. 20amp with 12/2 is already a no go.

Break the job down into two DP 20's, one for each set of two heaters.
You'd even have the option of 15's....50% of 22.125 = 11.0625

Then the 12/2 would be okay, with either the 15 or 20amp breakers.

Make sure you mark the whites with permanent black markers, tape/paint at both terminals.

Check the instructions for the heater, to make sure that
The temperature rating of the insulation, (it will be printed on
The wire in centigrade), is not exceeded.

And make sure the breakers you get will fit the service panel.

That's how I'd do it, but don't take my word, I'm a DIY'er myself

P.s. One of the guys 'll be along to grade me.


K
Helpful
tkrussell's Avatar
tkrussell Posts: 9,673, Reputation: 3698
Senior Electrical & Lighting Expert
 
#3

Oct 11, 2009, 04:45 AM


Kuxj is exactly correct, either one 30 amp circuit with #10-2 with ground cable or two 20 amp circuits with #12 with ground cable.
Helpful  (1)
KUXJ's Avatar
KUXJ Posts: 975, Reputation: 484
Senior Member
 
#4

Oct 12, 2009, 09:04 AM
Tk,
Something that's been buggin' me.

The reason I didn't acknowledge the 30amp DP breaker was, I was also taught that you take 80% of load and add it to the original total. Then you adjust up or down accordingly for the fixtures, I.e. Breakers, and wires.

So 80% of 17.7 = 14.16 + 17.7 = 31.86amps with buffer, and of course 10-2/ground would be underrated also by 1.86amps

And so I suggested two runs of 20amp DP.
It is also to my understanding that you don't want to go too high because if there is a problem the fixtures could/would overheat before the breaker would trip.

Am I incorrect in thinking this way?


K
Helpful
tkrussell's Avatar
tkrussell Posts: 9,673, Reputation: 3698
Senior Electrical & Lighting Expert
 
#5

Oct 13, 2009, 02:32 AM


No, you only add 25% to the load. Just like you stated, 17.7 amps plus 25%=22.12 amps. This one circuit requires a 30 amp circuit with #10 wire.
Helpful
stanfortyman's Avatar
stanfortyman Posts: 4,921, Reputation: 1351
Electrical & Lighting Expert
 
#6

Oct 13, 2009, 04:18 AM


Quote:
Originally Posted by KUXJ View Post

The reason I didn't acknowledge the 30amp DP breaker was, I was also taught that you take 80% of load and add it to the original total. Then you adjust up or down accordingly for the fixtures, I.e. Breakers, and wires.
Don't forget, this is only for certain loads as well. Such as electric heaters and continuous loads. Remember, very little in a residence is considered a continuous load.

General lighting and receptacle circuits do NOT use the "125% rule". That is already taken into account in the 3 watts per sq/ft load calculation for dwellings.
Helpful
KUXJ's Avatar
KUXJ Posts: 975, Reputation: 484
Senior Member
 
#7

Oct 13, 2009, 01:20 PM
Thank You Fellows, for clearing that up for me.

K
Helpful
chrisbosco's Avatar
chrisbosco Posts: 2, Reputation: 1
New Member
 
#8

Oct 13, 2009, 09:52 PM
Thank you all for the input. Didn't know about the load calculations.
I guess I should listen to big brother!
Helpful

Not your question? Ask your question View similar questions

 
Thread Tools Search this Thread
Search this Thread:

Advanced Search

Add your answer here.

Remove Text Formatting

Undo
Redo
 
Decrease Size
Increase Size
Bold
Italic
Underline
Align Left
Align Center
Align Right
Ordered List
Unordered List
Decrease Indent
Increase Indent
Insert Email Link
Wrap [QUOTE] tags around selected text
Wrap [CODE] tags around selected text
Wrap [HTML] tags around selected text
Wrap [PHP] tags around selected text
Wrap [YOUTUBE] tags around selected text
Notification Type:



Check out some similar questions!

How do I wire up a Marley electric baseboard heater? [ 2 Answers ]

This is my first post, so thanks in advance for any help. I'm finishing my basement & am installing a pair of Marley electric baseboard heaters in parallel. I've got the basics done: double 20 amp breaker, 12ga wire, Double line break thermostat. Here's the issue: The units will accept left or...

Wire sizing and conduit sizing [ 8 Answers ]

I am looking for confirmation on some of the info I have found and answers to a few missing pieces. This is regarding wire size and conduit size for service conductors from the meter to the breaker panel (about 30 ft away). Wire Size: 125A service needs #2 copper or 1/0 aluminum -- #6 copper...

Wire Sizing [ 2 Answers ]

I am rewiring a house in Mexico and following the 2002 NEC for wire sizing, grounding, circuits, etc for all work from the meter on. Service panel is 125A and will support air condition along with all other lighting and appliances. The utility company will only supply a 6 AWG overhead triplex...

Sizing Wire [ 3 Answers ]

I'm running a new 100amp sub about 40 ft from house. I've been reading but wanted to know you guys' opinion. Should I go with THWN #3 for my Hots/Neutrals. And #8 for EQ Gnd.? I'm kind of confused about the 90/75 degrees that rate this type wire. Also I understand about having to conduit...


View more Electrical & Lighting questions Search