    aaron2044's Avatar
    aaron2044 Posts: 4, Reputation: 1
    New Member
     
    #1

    Dec 28, 2008, 12:42 PM
    Air compressor motor
    I have a 230 volt 15 amp 60 hz 1 ph air compressor motor I want to wire. I am little confused when I open the switch there is 1 black, 1 white and one ground. I am to assume that the white is to be hot to be 230 volts. I'm running 14/3 through out my walls with a 20 amp dual pole breaker. So in conclusion I would go black to black, white to red and ground to ground and ingore the white from my panel. Would this be correct?
    KISS's Avatar
    KISS Posts: 12,510, Reputation: 839
    Uber Member
     
    #2

    Dec 28, 2008, 01:59 PM

    For 20A the wire must be 12 AWG.

    If the motor is dual voltage, make sure it's wired right and turns in the proper direction when connection to things that care.

    Think about it for a bit. If you ran 12/2 which is permissible, you would have black and white and ground. The ends of the white wire would be taped red.

    You can run 12/3 w/ground and ignore the white wire if you like.
    aaron2044's Avatar
    aaron2044 Posts: 4, Reputation: 1
    New Member
     
    #3

    Dec 28, 2008, 03:01 PM

    The reason for 20 amp breaker is you can't go more than 75% of the breaker but you can fully load the wire. Since the motor draws 15 you would be OK with 14 gauge, in theroy but you might as well go to 12 gauge, if you get 12/2 heater wire, it come with red black ground, so no confusion
    Tev's Avatar
    Tev Posts: 232, Reputation: 20
    Full Member
     
    #4

    Dec 29, 2008, 02:41 PM

    240.4(D) of the national electric code specifies maximum breaker size for small gauge wires. For 14 AWG the maximum breaker size is 15 amp. If you need a 20A breaker then you must use 12AWG or larger wire.
    benaround's Avatar
    benaround Posts: 69, Reputation: 6
    Junior Member
     
    #5

    Dec 29, 2008, 04:12 PM
    Tev,

    Just so you know, 240.4(G) or table 240.4(G) allows us to use 430 Parts III-VII for

    OP for specific conductor applications. On a single phase motor with an instantaneous trip

    c.b. you can go 800% larger OCPD if needed to start the motor. In the case of a #14

    Gage wire you could use up to a 120a c.b. and be in compliance with the NEC.
    Tev's Avatar
    Tev Posts: 232, Reputation: 20
    Full Member
     
    #6

    Dec 29, 2008, 10:34 PM

    I'm sorry, I don't believe that applies here Ben. I'll explain my reasons.

    1. The compressor needs a disconnecting means. That will likely mean a receptacle outlet.
    2. The fact that he is sizing the circuit to accommodate his compressor does not mean nothing else will ever plug into the receptacle.
    3. The receptacle has to be 240v 20a rated,
    Anything with a 240v 20a plug on it could end up in the receptacle when the compressor is not in use, including a heater.

    For those reasons article 430 should be used for sizing the breaker but the wire and receptacle should be sized to match the breaker's ampacity. I mean really, what's the cost difference between 12/2 and the 14/3 he was going to use. Go for the safety.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

A/c compressor motor [ 3 Answers ]

My a/c compressor motor will not start when I turn on down the thermastat unless I go outside and manually spin it to get it started. It will run for about 15 minutes and then it will stop again. I have to turn the air off for about 30 minutes and then I can turn it on and manually start it again...

New compressor motor [ 3 Answers ]

Tried to connect my air compressor up and the breaker will not stay on. Other ansers make me believe this is a short, however, the wiring had no problems before and the motor is new. The breaker is a 30 amp, the motor only needs a 25.

AC Compressor fan motor wiring 3 versus 4. [ 3 Answers ]

Need wiring directions to the following mess. 3 (old motor) verus 4 (new motor) wires and different colors to boot. I have a Goodman Mfg. Compressor Model CK30 1B that had a GE P870S motor that went out. Old Capacitor (GE #97F9834) is a three plug version. GE Motor Wiring: (Blk, Brn, and...

Compressor motor shuts off. [ 1 Answers ]

The compressor motor stopped running,(I was told it was bad) so I replaced it. When I started the unit back up it ran for a few minutes, but when the compressor tried to kick in it shuts off. I tried it several times but whenever the compressor tries to kick in it keeps shutting off. They gave me a...

Compressor Fan Motor keeps shutting off [ 1 Answers ]

With the AC on and running the temperature started to rise in the house. I put my hand next to the register. Air was blowing but was not cool air. I went outside and the compressor fan motor wasn't blowing. On another occasion the same thing happened and I went outside and the fan motor was making...


View more questions Search