    Air compressor ac motor flips breaker after delay
    Hello thank you for taking the time to look/answer my question. That being said my problem is with a ac motor for a air compressor it worked fine then all of a sudden it started to throw the breaker. It will start and run fine for about 5-7 seconds then it will flip the breaker. Any advise will be appreciated.

    Here are some specs for the motor

    a.o.smith
    115v
    15a
    3450rpm
    Model#d24228
    Ph 1

    I believe it to be single phase but not sure it does have two capacitors
    Thank you
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Sep 17, 2007, 05:08 PM
    You may want to swap the wire to another breaker of the same size to determine if the breaker is OK.

    Check the breaker for a loose wire connection and be sure the tab the breaker plugs onto is clean. Check the underneath of the breaker where the jaws plug onto the tab in the panel. Any looseness or corrosion will create heat that can trip the breaker.
    rflcam's Avatar
    rflcam Posts: 5, Reputation: 2
    New Member
     
    #3

    Sep 17, 2007, 05:15 PM
    I have tried it in many outlets around the house and it seems to always do the same thing
    I even tried it at my friends house

    Thank you for your time
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #4

    Sep 17, 2007, 05:18 PM
    OK then the motor is getting hot or overloading for some reason. Need to have it checked out. Check that rotation is proper. If you have an amp-probe, you can check the starting and running amps. This is similar to having your blood pressure check, without measuring the amps, everything is nothing but a guess.
    rflcam's Avatar
    rflcam Posts: 5, Reputation: 2
    New Member
     
    #5

    Sep 17, 2007, 05:23 PM
    HA I just found out from my friend that I let borrow it that he left it outside in a storm and it got soaked so that probably means its gone

    That's the last time I loan out tools!
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #6

    Sep 17, 2007, 05:29 PM
    Well there you go, too bad he did not mention it when he returned it.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Ballpark for compressor fan motor replacement [ 12 Answers ]

Hello, all. A few weeks ago the compressor fan motor on our 3 ton Trane heat pump apparently died. The unit was only 4 years old, so the part was covered by the Trane warranty. However, the labor to replace the part was not covered. (For what it's worth, the model # of the heat pump is...

AC Compressor fan motor wiring 3 versus 4. [ 2 Answers ]

I tried the suggestion from "lemetellu" (see below) and it worked however the fan will not cut off when compressor does. Any more suggestions... Any help is appreciated. Motor wiring: Black wire: to "Line" Yellow wire: to "Line" Solid Brown Wire: to one side of Cap Brown Wire with...

Compressor motor shuts off. [ 1 Answers ]

The compressor motor stopped running,(I was told it was bad) so I replaced it. When I started the unit back up it ran for a few minutes, but when the compressor tried to kick in it shuts off. I tried it several times but whenever the compressor tries to kick in it keeps shutting off. They gave me a...

Compressor Fan Motor keeps shutting off [ 1 Answers ]

With the AC on and running the temperature started to rise in the house. I put my hand next to the register. Air was blowing but was not cool air. I went outside and the compressor fan motor wasn't blowing. On another occasion the same thing happened and I went outside and the fan motor was making...

Main breaker flips off before lesser breakers go [ 1 Answers ]

My problem is the main breaker in the house will flip off before any of the smaller specific breakers flip off. Something is getting overloaded but the smaller breakers are not taking the load.


View more questions Search