| Main breakers are not required in these panels fed by the actual Main Service Disconnecting Means, which are the two 200 amp Mains at the meter.
You may have Main breakers in the panels if desired for convenience and redundant protection, but not required by Code.
Just be sure to do the grounding of the neutral at the meter/disconnect combo, and use 4 wire feeder to both panels, and keep the neutral and equipment ground separate in both panels. |