    30 amp spa connected to 50 amp breaker
    I recently purchased a new hot tub. The tub arrived and it only requires 30 amps.
    The electrician hooked it up to 50 amp breakers (outside box and inside on the main) Is this safe??
    Stratmando's Avatar
    Stratmando Posts: 11,188, Reputation: 508
    Uber Member
     
    #2

    Dec 11, 2009, 05:17 PM

    If the 50 GFI is outside, you can change Panel Breaker to a 30 AMP.
    What do you have and where.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #3

    Dec 12, 2009, 05:07 AM
    The circuit is per code, but needs to comply with the instructions for the tub.

    This also assumes the 50 amp circuit is wired with #6 copper wire.
    pistolpieter's Avatar
    pistolpieter Posts: 3, Reputation: 1
    New Member
     
    #4

    Dec 12, 2009, 12:08 PM

    I bet the wire is sized for 50 amps so he installed it because of that. Was the circuit existing or did he install it? As long as the wire is sized for the larger breaker then this is perfectly fine.
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #5

    Dec 12, 2009, 12:40 PM

    Pistol,

    I disagree with you. You cannot protect a 30 amp circuit with a 50 amp breaker.

    The delay in the breaker tripping could get someone killed.

    A 30 amp circuit needs a 30 amp breaker.
    Stratmando's Avatar
    Stratmando Posts: 11,188, Reputation: 508
    Uber Member
     
    #6

    Dec 12, 2009, 05:19 PM

    Donf, I don't know that he said that.
    Wire sized for the larger Breaker would be #6(or larger).
    Missouri Bound's Avatar
    Missouri Bound Posts: 1,532, Reputation: 94
    Ultra Member
     
    #7

    Dec 12, 2009, 07:13 PM
    If the tub mfg. specifies that the tub should be on a 30 amp circuit, change the breaker. The wiring is fine.
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #8

    Dec 13, 2009, 11:29 AM

    Strat,

    I'm just concerned that the original poster may leave the 50 Amp breaker in place.

    I agree, the larger wire is fine.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

What size fuse should I use in my disconnect for a 27 amp draw on a motor [ 1 Answers ]

I am running a piece of equipment that draws 27 amps which is on the nameplate of the motor but keep blowing 30 amp fuses . What size fuse should I have to protect this motor. Can I upgrade the fuse for say 35 amps.

What is farady's cage & how it works [ 3 Answers ]

Dar Sir, What is farady's cage & how it works

My furnace won't light diagnostic light is green, & yhe thermostat says heat is on [ 1 Answers ]

Any ideas what's wrong it's a coleman mobile home furnace

Can I run a 1300 watt converter on a dedicated 15 amp circuit [ 2 Answers ]

1300 watt converter on dedicated 15 amp circuit.

Are blood clots after a d&c normal? [ 1 Answers ]

I just had a hysteroscopy d&c and my period stopped for a week and a half, and now my period is heavier than ever and I am getting big blood clots. Does anyone know if this is normal? By the way the same day I got my d&c they insterted an IUD.


View more questions Search