    30 amp buss fuse - TL vs W
    RE: electric clothes dryer fuse to replace

    What is the difference between these 30 amp buss fuses -- TL vs W?

    When should I use TL and when W?
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Feb 16, 2008, 06:05 AM
    The W series is a fast acting fuse, and the TL series is a Time Delay.


    Time delay is designed to allow the high inrush current from a motor starting to flow, and allow the motor to start. The inrush current reduces down to normal running current after a few cycles.

    A W offers more precise protection, if needed, by limiting current to a level closer to the fuse rating. Depending on the size motor, or other device with high inrush current, a W fuse may open if the inrush current is too great.


    For most purposes, including this dryer, the Time Delay fuse is recommended.

Not your question? Ask your question View similar questions

 

Add your answer here.


Check out some similar questions!

3-amp fuse on circuit board [ 7 Answers ]

I've been having an intermittant problem where the 3-amp fuse on the circuit board keeps burning out. Lately, the problem has occurred in the late afternoon (3-7pm) such that when I replace the fuse, it will last for 3-4 minutes before blowing again. If I wait until late in the evening to turn on...

Keeps blowing 3 Amp Fuse on Control Panel. [ 1 Answers ]

I Have A Carrier (58gsc)upflow Furnace & A/c Unit, Which Is 18 Years Old. When I Tried To Turn The Heater On , Only Blower Came On & Would Not Turn Off Unless Disconnected From Electricity. Replaced Sofar Control Unit, Thermostat,transformer Was Blown,& Finally The Limit Switch. When I...

Looking for help with my internet buss [ 5 Answers ]

I'm trying build me a web internet store like bussines www.soldiersandgaer.com Going need rebuild my site need advice on building Also any know places to find whole sale product or drop shippers I'm Tommy

3 amp fuse blown [ 2 Answers ]

I have a Carrier Gas Furnace that is blowing the 3 amp fuse for the secondary 24 Vac. I have replaced the fuse and after the heat is on for awhile the fuse will blow and then I have cool air blowing. Please advise on how to troubleshoot problem.Thanks


View more questions Search