| A typical range is 8000 watts or larger, and needs a minimum of a 40 amp circuit, which is a 40 amp 2 pole breaker, and #8 copper wire in a 4 wire cable, and a 40/50 amp 4 wire receptacle.
Sounds like what you have is not sufficient.
You may use the 30 amp circuit, but may have problems tripping the breaker if all the range buners and oven is used all at the same time. |