    208 volt3 phase y to single phase 120 volt
    Supply is from 75 kva transformer, 3 phase delta /y three wire feeding a 30 amp breaker. 100 feet down stream is a junction box that I want to tap and produce a 120 v single phase ( 20 amp CB) supply. The junction box feeds a 6 amp motor
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Nov 28, 2007, 03:57 AM
    What is your question?

    Since you only have 3 phase 3 wire, you will need a minimum 2500 watt transformer to create the 120 volts, and ground the neutral of the 120 volt output.
    pelle's Avatar
    pelle Posts: 96, Reputation: 0
    Junior Member
     
    #3

    Nov 28, 2007, 11:38 AM
    Are you saying you have a 3 phase 120/208 4 wire y system or is a delta 240 or 480 (common but old here).. If it is 208v phase to phase.. the phase to ground reading should be 120v on each of the phases.. if it is a delta than phase to ground and phase to phase would read the same.
    Please provide more info or as tk asks a question..
    chotchy's Avatar
    chotchy Posts: 2, Reputation: 1
    New Member
     
    #4

    Nov 28, 2007, 08:04 PM
    I have a Delta/Wye 480v/208v 3 phase THREE wire Wye circuit (no neutral). 100 feet away I want to tap the 208 3 phase and develop a 120 v single phase circuit. Since there is no neutral at this point how do I go about getting 120v neutral to phase when I haVE no neutral
    Thanks
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #5

    Nov 29, 2007, 07:13 PM
    Feed a single phase 2.5 Kva transformer, 208 VAC Primary/ 120 volt Secondary, and ground one of the 120 volt legs to a grounding electrode, building steel is sufficient if steel frame.

    Be sure to provide both Pri and Sec overcurrent and short circuit protection.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Difference between single phase and 3-phase motors [ 4 Answers ]

Difference between single phase and 3-phase motors

Three phase vs. Single phase [ 3 Answers ]

What benefits would you have running a three phase service as opposed to running single phase.

Changing out 3-phase motor for single Phase [ 1 Answers ]

Besides matching the mounts & drives, are there wiring/switching issues changing out a 220-3phase for 220-S-Phase. I am interested in switching motors in a commercial diswasher.

Single phase vs 3 phase [ 1 Answers ]

I have a situation where a customer wants to introduce/hookup an single phase 3 wire 18 kVA UPS to a 3 phase 4 wire panel and the UPS will be used to power a single phase 3 wire panel. The only thing the 3 phase panel will be used for is to power the single phase UPS. The entire building is 3...

3 phase 208 volt/120 volt .load [ 1 Answers ]

I am trying to hook up a commercial espresso machine which has a 220 line. My existing electrical box is a 3 phase 208 volt/120 volt. Would this be sufficient to handle this?? Thank you


View more questions Search