    200 amp service with a 200 amp outdoor breaker
    I need to know how to wire a 200 amp outdoor breaker enclosure.I have 4/0 scu cable for my service head to the meter,and 4/0 scu from meter to breaker enclosure.Then from the breaker enclosure I have 4/0 ser cable to my panel.What is the proper wiring method in the enclosure,please help.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Aug 25, 2006, 01:40 PM
    The top two lugs on the meter and breaker are Line, the bottom are Load. The two hots from the street connect to the Line of the Meter, the two hots Load from the meter connect to the Line of the breaker, the two Load of the breaker connect to the main lugs on the panel.

    The two whites in the meter connect to the neutral lug in the meter, which is bolted directly to the steel can .The two whites connnect to the neutral lug in the breaker. Here is whre you drive the green screw provided through the neutral lug into the steel breaker can. Also at this lug is where the bare going to the panel, and the #4 copper wire going to the water ground and ground rods connect.

    The white connects to the neutral bar in the panel, which is insulated from the can. Do not drive a green screw into the can here.

    The bare connects to the equipment ground bar bolted directly into the panel can.

    All branch circuits white connect to neutral bar, and all greens and bare ires connect to the ground bar. Never the two meet again beyond the main breaker.

    Also be sure to use anti-oxidant compund on each aluminum wire connection and properly torque each connection.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Outdoor outlets not working. HELP! [ 2 Answers ]

Hello, Here's my dilemma: I have 3 ooutdoor outlets along the back of my property. As far as I know all have worked up until this morning. There was a terrible storm yesterday where flooding, high wind and long periods of down pours were present; now none of the electrical outlets are working. I...

Outdoor Balcony Fan Light.. [ 8 Answers ]

Hello everyone! I have a fan/light unit that is going to be installed on the third floor balcony of a vacation home. Are any special requirements in order since it is outside although it does have a covered roof and is 3-sided. Anhy help appreciated. Also I have (2) receptacles on each floor...

What Wire do I use for overhead outdoor use? [ 1 Answers ]

Hello, I have a detached garage about 150' from the main. I want to install a sub-panel in it. What kind of wire do I use to run it the same way it comes into the house (overhead). Does Home Depot sell it? I have two garages and have already run their #2 or #3 underground to it. But this one would...

Outdoor Spa and lighting [ 1 Answers ]

Dear all, Happy holiday's I have two 40amps in the main box that feeding the AC Unit. I would like to know if its possible and code pass in new Jersey, Piscataway. To tap into that conduit at a junction point and extend the required wires in a conduit 30-40 feet to a Spa 50/AMPS @ 240...

Outdoor wiring for pool [ 2 Answers ]

We are thinking of getting a pool for the yard, the pool place said you can't use extension chrods and the best bet is to have a electrican come in and build a trench out side and run the wires underground. I have no clue what so ever about wiring. Does anyone have any idea how much that might...


View more questions Search