    110 v outlet off a 220 while maintaining 220v for a water pump
    I have a 10-2 with ground 220 line to a water pump with no access to a 110 circuit. I need to install a 110 circuit to run a lights in the pumphouse. Can I do this by using a 1 hot lead and the ground wire as neutral to get the 110 power and then pound a ground stake in and connect the 110 ground wire to it? My purpose is to operate one light by a switch and the other(100-150 W) on a thermostat to provide some heat on nights when the temp drops into the 20's.

    Thanks, Dale
    KISS's Avatar
    KISS Posts: 12,510, Reputation: 839
    Uber Member
     
    #2

    Nov 11, 2007, 03:58 PM
    Nope.

    But I'll give you two other ideas.

    1) Step down transformer (240-120)
    2) Wire two 120 Volt lamps in series
    3) Fluorescent lighting with a 220 ballast.. 277 is used a lot in commercial lighting and the ballasts may be able to use 240.

    Just remember to use a dialectric grease or Vaselene on the pins or threads.

    How much power do you need? What kind of lighting were you thinking about?

    Looks like it didn't read it enough. I guess option#3 is out. #1 and #2 are viable.
    KISS's Avatar
    KISS Posts: 12,510, Reputation: 839
    Uber Member
     
    #3

    Nov 11, 2007, 05:39 PM
    Here is a cheap fixture: hdsupplysolutions.com - Linear Fluorescent Fixtures

    Here is a 750 VA (Watt) Transformer.

    Step Down Transformer To Use Overseas- THG750

    EDIT: Added transformer link

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

110 volt versus 220 volt mini heat pump [ 6 Answers ]

I have enclosed my screened porch to create more living space(Florida Room). I am using a single zone mini split ductless heat pump for heating and cooling. It has been calculated that I need a 12,000 BTU unit. However, most of these units are available in 110 volts and 220 volts. The 220 models...

Water heater 110 or 220 [ 10 Answers ]

Looking to buy a kenmore 20 gallon water heater.110 has 2000 watt element 220 has 4000 element.I was told either way they will use the same amount of electric just the 220 will heat up more quick .Is this the case.I ask because sister said she had a 110 dryer once and electric went through the...

Assemble a 220 volt outlet from two 110 volt circuits [ 5 Answers ]

I need help making a temporary 220 volt outlet cord. I have the female 220 v receptacle and two extension cords. I need this to connect a window AC. The electrician cannot come until mid next week. It is very hot here. He told me to put one these cords together for a temporary fix. He warned...

220 to 110 [ 7 Answers ]

I'm wanting to run a 110 outlet off my 220 serface unit how do I go about doing this?:confused:

Getting 110 from 220 [ 3 Answers ]

I have a 3-wire 220V going to my well house. I am wanting to come off the 220 to a 110 outlet. I realize this is not the safest thing to do but it is only temporary. My question is, I know I use one wire so I cut let's say the white wire and connect it to one side of this GFI outlet, Do I connect...


View more questions Search