Ask Experts Questions for FREE Help !
Ask

100 amp wire size

Asked Jan 26, 2008, 03:56 AM — 3 Answers
I have a 150 amp service feeding a 100 amp main lug sub panel. I need to move the sub panel to another location during a remodel. My question is what size copper wire is needed to lengthin the panel feeds, including the ground. The total distance from the main is approx. 40 feet. Planning to use insulated bugs on the mains.
My plan is to pull all necessary circuits from existing panel location into the attic and use a getter box to make up joints to lengthen the circuits. This box being a 10"x10" galvanized should be grounded. Is this correct?
In additon to these concernes, I have investigated the existing sub panel and found whoever installed it landed the ground from the main to the neutral buss bar. This should have its own ground buss bar. Am I correct on this?
Any helo would be greatly appreciated.

3 Answers
tkrussell's Avatar
tkrussell Posts: 9,673, Reputation: 3698
Senior Electrical & Lighting Expert
 
#2

Jan 26, 2008, 04:16 AM


#4 THHN/THWN copper is the minimum size wire allowed for a residential 100 amp feeder.

What do you mean that you plan to bug the main? A 100 feeder for a subpanel needs to be connected to a 2 pole 100 amp circuit breaker. It cannot be bugged onto the main lines feeding the main panel.

All metal boxes in an electrical system needs to be grounded.

Yes, the equipment ground must be separated from any neutral bar in a subpanel. The neutral bar is to be insulated from ground, and equipment ground bar is bolted directly to the panel box.
Helpful
wire nut's Avatar
wire nut Posts: 3, Reputation: 1
New Member
 
#3

Jan 26, 2008, 05:13 AM
I do in fact intend to bug onto the 100 amp main panel feed to the sub panel. Didn't mean to scare you. What is the correct size ground wire required? Is this also a #4?
Helpful
tkrussell's Avatar
tkrussell Posts: 9,673, Reputation: 3698
Senior Electrical & Lighting Expert
 
#4

Jan 26, 2008, 05:20 AM


So you plan to connect directly to the 150 amp rated main incoming feeder ahead of the main breaker? With this plan there will be no overcurrent or short circuit protection at all.

If you plan to connect to main lines downstream of the 150 amp breaker, you would have both protections, but the 100 amp feeder line will not be protected properly for overcurrent.

Neither plan is allowed, or a safe practice.

Is the "100" amp in the second post a typo? First post stated a 150 amp main.

I assume the ground wire you refer to is the equipment ground that is needed for the new feeder. This would be a min of #8 copper.
Helpful

Not your question? Ask your question View similar questions

 
Thread Tools Search this Thread
Search this Thread:

Advanced Search

Add your answer here.

Remove Text Formatting

Undo
Redo
 
Decrease Size
Increase Size
Bold
Italic
Underline
Align Left
Align Center
Align Right
Ordered List
Unordered List
Decrease Indent
Increase Indent
Insert Email Link
Wrap [QUOTE] tags around selected text
Wrap [CODE] tags around selected text
Wrap [HTML] tags around selected text
Wrap [PHP] tags around selected text
Wrap [YOUTUBE] tags around selected text
Notification Type:



Check out some similar questions!

Condo/Apt. New 100 amp service - BX wire size? [ 12 Answers ]

Hi All! I currently have an old 40 amp service in my pre-war condo. We are allowed to run BX securely attached for a new service. The distance is 250 feet. I am looking to get a 100 amp service. What size BX cable should be used for this? Do they make BX large enough for a 250 foot 100 amp...

Wire service, wire gauge 100 amp [ 1 Answers ]

I'm installing a 100 amp service in the backyard with a separate meter on a pole next to sub-suface power tranasformer. I have a 100 amp meter box on one side of the pole and a 100 amp braker panel with a 100 amp main breaker on the other side. I'm going to place in it a 15-20 amp breaker for gfi...

100 amp sub panel wire size [ 2 Answers ]

I now have the 100 amp breaker installed in my load panel. I will run wiring from the load panel to a 100 amp sub-panel in an unground 80 schedule PVC. I believe I need to use #2 wire for the the hots and the neutral. If this is correct, then what size ground do I use? Number 6? The sub- panel...

Secondary 100 Amp Feeder Wire Size [ 3 Answers ]

Hello to all. I am running a feeder wire in 2" conduit from my 100 amp breaker in my house panel to my 100 amp garage panel approximately 160' away. I am wondering if #1-#1-#2 Aluminum is sufficiant with a #6 Copper ground. Thanks for the help.

Wire size in a 100 amp breaker [ 1 Answers ]

I was wondering if a 2/0 wire will fit in a siemens 100 breaker? Thanks for your help


View more Electrical & Lighting questions Search