  • Feb 2, 2009, 11:21 PM
    cornelboots
    Electrical load computation formula
    How can I conpute the electrical load (ampere) of a building
  • Feb 2, 2009, 11:22 PM
    cornelboots

    How to compute electrical load of a building
  • Feb 7, 2009, 03:18 AM
    sarnian
    Quote:

    Originally Posted by cornelboots View Post
    How can i conpute the electrical load (ampere) of a building

    That depends mainly on the use of that building. Domestic / office / factory each have different load influences.
    Can you provide some details here on the building use, size, location, weather influences, etc ?
  • Apr 3, 2009, 01:29 AM
    2968

    What size of wire and breaker use for 60kw heater
  • Apr 18, 2009, 10:48 PM
    sathe1963
    Quote:

    Originally Posted by 2968 View Post
    what size of wire and breaker use for 60kw heater

    please let us know whether the heater is 3ph, n or single phase?
  • Apr 18, 2009, 10:49 PM
    sathe1963
    Quote:

    Originally Posted by 2968 View Post
    what size of wire and breaker use for 60kw heater

    Also what is the supply voltage?
  • Apr 17, 2011, 10:25 PM
    dheylyn
    What size of wire use for 60kw?
    It depends on the supply voltage 440/220 or single ph.or 3phase.
    So if we know the supply voltage & the phase we can compute the right size
    Of wire and breaker
  • Nov 16, 2011, 04:49 AM
    mannyjoson
    What is the maximum or full load of 300kva 3 phase transformer?
  • Nov 16, 2011, 05:39 AM
    tkrussell
    300 Kva is the max load.

    if you are looking for the load in amps, need to know the voltage.

    For example, if the voltage is 480, then:

    KVA= I*E*1.73

    I = KVA / E*1.73

    I = 300 KVA / 480*1.73

    Amps is 361.27
  • Dec 9, 2011, 10:53 PM
    jhaysome
    Calculation of electrical of cart
  • Dec 10, 2011, 03:52 AM
    tkrussell
    Need more details.
  • Apr 24, 2013, 12:25 AM
    enegue
    30 amps is safest to use in a 60kw heater
  • Apr 24, 2013, 02:52 AM
    hfcarson
    enegue...
    Check the dates on the posts... over two years old...