    300 amp wire size
    I want to install a 300amp t from the main panel this is a commercial . What gauge and type of copper wire and what size conduit whould I use.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Aug 17, 2010, 12:47 PM
    And what if I told you #2 in 4 inch conduit? Would you believe me?

    Where is this located?

    Phase?

    What type conduit?

    Location of conduit?

    Are you an electrician?

    Commercial what? Elaborate on the building.
    wplash420's Avatar
    wplash420 Posts: 2, Reputation: 3
    New Member
     
    #3

    Aug 28, 2010, 03:03 PM
    Why would you tell someone #2 in a 4 inch conduit... I mean if your going to with someone... just tell them to pound sand or something. Don't intentionally give them the wrong information... even if its in the form of a question. That's dangerous and stupid.
    wplash420's Avatar
    wplash420 Posts: 2, Reputation: 3
    New Member
     
    #4

    Aug 28, 2010, 03:07 PM

    Oh and by the way... its 350 kcmil in a 2 1/2 inch conduit for the average commercial installation into a 300 amp panel.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #5

    Aug 29, 2010, 04:11 AM
    Since when is information in a question providing that information?

    This is not Jeopardy. In my world a question does not provide information.

    My point is a generic question was asked with a great deal if detail missing. And my other point is that anyone installing a 300 amp commercial feeder better have some knowledge and experience.

    I am glad your able to speculate on the details that were not provided.

    If it is single phase, and 4 - 350 MCM copper THHN/THWN can fit in a 2.5 " PVC Sch 40, the 3- #350 MCM and 1 equipment ground will fit.


    If this question involves 3 phase, then what?

    If Sch 80 is used, then only 3 # 350 MCM THHN/THWN will fit.

    Assuming you know all the missing details and situations is dangerous.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Wire size & conduit size for 60 am subpanel 150 from source [ 9 Answers ]

Indiana question: I want to install a 60amp subpanel 150 feet from the main panel. This is all exposed runs both inside and out in a commercial envirenement. What gauge and type of copper wire and what size conduit whould I use. How often should insert a junction box in the run. John

Can I run a 50 amp subpanel if a 100 amp main if so what size wire [ 1 Answers ]

Can I run a 50 amp subpanel from a 100 amp main and if so what size wire

Wire size wire & circuit breaker do I need for a 15.8 range [ 2 Answers ]

What size circuit breaker & wire size do I need rfor a 15.8 raqnge ?

Sub Panel AMP Size and Supply Wire Size [ 1 Answers ]

I would like to install a sub panel in my garage I was told to run 6/3 Romex to supply the sub panel and have done so. The run is about 65 feet and I am now wondering after reading this site what is the max I can get for this size wire? I plan to supply a compressor (20 amp) and the garden...

Wire Size for 150 amp service 300 feet [ 1 Answers ]

I need to take electrical service 300 feet to my barn. I want to take a 150 amp service. What wiresize to I use for this effort.


View more questions Search