I have a Heil NTG3100GFA4 furnace and this evening just the inducer motor would start. The pilot (electronic) don't light and start the main burners.
Problem solved
After searching all night, I finally found the problem. The rubber hose on to pressure switch had a break in it. I did a temp repair until the stores open.