I would definately get the installers back out. There are many things that could have happened. May not have gotten charge right, or may even have forgot to open service valves. Usually you pull all refrigerent into condenser using the service vavle, when you make repairs to coil or line set. Then you pull a vaccum on line set and a-coil, and open service valves. This way you dont have to reclaim refrigerant, or recharge system. But i have seen people forget to open service vavles. I would not run system untill you get the installers back out. If you do, wether it be a low charge, or closed service valves, etc etc, running the system may cause damage to compressor or (if a low charge) freezing of a-coil which may result in water damage to furnace controls. Please let us know what the tech finds.