Bdunbar
Jan 24, 2009, 09:59 PM
I have a xv90 trane gas furnance. The inducer motor runs, but does not pull enough vacuum to close the pressure switches. I've already disconnected the vent, checked the condensate drain and vacuum hoses. The vacuum line does not connect directly to the inducer motor. Any help would be appreciated.

wmproop
Jan 25, 2009, 08:12 AM
is the vacuum hose in good shape? Free of dryrot ,cracks,or holes

Bdunbar
Jan 25, 2009, 06:28 PM
Thanks for the response, but I solved it. Plastic bag in the intake pipe.